Simplified P-M interaction curve model for reinforced concrete columns exposed to standard fire  

Lee, Deuck Hang (Department of Architectural Engineering, University of Seoul)
Cheon, Na-Rae (Metallic Materials and Mechanical Engineering Team, Korea Testing & Research Institute)
Kim, Minsu (Department of Architectural Engineering, University of Seoul)
Lee, Jungmin (Department of Architectural Engineering, University of Seoul)
Oh, Jae-Yuel (Department of Architectural Engineering, University of Seoul)
Kim, Kang Su (Department of Architectural Engineering, University of Seoul)
Publication Information
Computers and Concrete / v.19, no.5, 2017 , pp. 545-553 More about this Journal
Abstract
In the authors' previous study, an axial force-flexural moment (P-M) interaction curve model was proposed to evaluate fire-resisting performances of reinforced concrete (RC) column members. The proposed method appeared to properly consider the axial and flexural strength degradations including the secondary moment effects in RC columns due to fire damage. However, the detailed P-M interaction curve model proposed in the authors' previous study requires somewhat complex computational procedures and iterative calculations, which makes it difficult to be used for practical design in its current form. Thus, the aim of this study was to develop a simplified P-M interaction curve model of RC columns exposed to fire considering the effects of fire damage on the material performances and magnitudes of secondary moments. The simplified P-M interaction model proposed in this study was verified using 66 column fire test results collected from literature, and the verification results showed that the proposed simplified method can provide an adequate analysis accuracy of the failure loads and fire-resisting times of the RC column specimens.
Keywords
reinforce concrete column; simplified; fire resistance; P-M interaction curve; secondary moment; slenderness ratio;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 ISO 834 (1999), Fire-Resistance Tests-Elements of Building Construction-Part 1: General Requirements, International Organization for Standardization, Geneva, Switzerland.
2 Johnson, P. (2008), "P-M characteristics of reinforced concrete sections", M.S. Dissertation, Clemson University, Clemson, U.S.A.
3 Kang, H., Cheon, N.R., Lee, D.H., Lee, J., Kim, K.S. and Kim, H. Y. (2017), "P-M interaction curve for reinforced concrete column exposed to elevated temperature", Comput. Concrete, In Press.
4 Kang, H., Lee, D.H., Hwang, J.H., Oh, J.Y., Kim, K.S. and Kim, H.Y. (2015), "Structural performances of prestressed composite members with corrugated webs exposed to fire", Fire Technol., 52(6), 1957-1981.
5 Kodur, V., Raut, N. and Mao, X. (2013), "Simplified approach for evaluating residual strength of fire-exposed reinforced concrete columns", Mater. Struct., 46(12), 2059-2075.   DOI
6 Lee, S.J., Lee, D.H., Kim, K.S., Oh, J.Y., Park, M.K. and Yang, I.S. (2013), "Seismic performances of RC columns reinforced with screw ribbed reinforcements connected by mechanical splice", Comput. Concrete, 12(2), 131-149.   DOI
7 Lie, T.T. and Irwin, R.J. (1993), "Method to calculate the fire resistance of reinforced concrete columns with rectangular cross section", ACI Struct. J., 90(1), 52-60.
8 Rout, N.K. and Kodur, V.K.R. (2011), "Response of high-strength concrete columns under design fire exposure", J. Struct. Eng., 137(1), 69-79.   DOI
9 Lie, T.T. and Woolerton, J.L. (1988), "Fire resistance of reinforced concrete columns-test results", Internal Report No. 569, National Research Council Canada, Ottawa, Canada.
10 Rodrigues, J.P.C., Laim, L. and Correia, A.M. (2010), "Behaviour of firber reinforced concrete columns in fire", Compos. Struct., 92(5), 1263-1268.   DOI
11 Tan, K.H. and Tang, C.Y. (2004), "Interaction formula for reinforced concrete columns in fire conditions", ACI Struct. J., 101(1), 19-28.
12 Tan, K.H. and Yao, Y. (2003), "Fire resistance of four-face heated reinforced concrete columns", J. Struct. Eng., 129(9), 1220-1229.   DOI
13 Wang, Y., Burgess, I., Wald, F. and Gillie, M. (2012), Performance-Based Fire Engineering of Structures, CRC Press, New York, U.S.A.
14 Yao, Y. and Tan, K.H. (2009), "Extended rankine approach for biaxially loaded steel columns under natural fire", Eng. Struct., 31(5), 1024-1031.   DOI
15 Yao, Y., Tan, K.H. and Tang, C.Y. (2008), "The effect of a shear bond in the rankine method for the fire resistance of RC columns", Eng. Struct., 30(12), 3595-3602.   DOI
16 Yeo, I.H. (2012), "A proposal for load ratio of reinforced concrete column subjected to standard fire", Ph.D. Dissertation, University of Seoul, Seoul, Korea.
17 Han, C., Han, M. and Heo, Y. (2009), "Improvement of residual compressive strength and spalling resistance of high-strength RC columns subjected to fire", Constr. Build. Mater., 23(1), 107-116.   DOI
18 ACI Committee 318 (2011), Building Code Requirements for Structural Concrete and Commentary, Michigan, U.S.A.
19 Choi, Y.H., Foutch, D.A. and LaFave, J.M. (2006), "New approach to AISC P-M interaction curve for square concrete filled tube (CFT) beam-columns", Eng. Struct., 28(11), 1586-1598.   DOI
20 Choi, Y.H., Kim, K.S. and Choi, S.M. (2008), "Simplified P-M interaction curve for square steel tube filled with high-strength concrete", Thin Wall Struct., 46(5), 506-515.   DOI
21 Hu, X., Guo, H. and Yao, Y. (2015), "Interaction approach for concrete filled steel tube columns under fire conditions", J. Build. Eng., 3, 144-154.   DOI
22 ISO 834 (1999), Fire-Resistance Tests-Elements of Building Construction-Part 1: General Requirements, International Organization for Standardization, Geneva, Switzerland.