Browse > Article
http://dx.doi.org/10.12989/was.2017.25.5.433

A study on the average wind load characteristics and wind-induced responses of a super-large straight-cone steel cooling tower  

Ke, S.T. (Department of Civil Engineering, Nanjing University of Aeronautics and Astronautics)
Du, L.Y. (Department of Civil Engineering, Nanjing University of Aeronautics and Astronautics)
Ge, Y.J. (State Key Laboratory for Disaster Reduction in Civil Engineering, Tongji University)
Zhao, L. (State Key Laboratory for Disaster Reduction in Civil Engineering, Tongji University)
Tamura, Y. (Center of Wind Engineering Research, Tokyo Polytechnic University)
Publication Information
Wind and Structures / v.25, no.5, 2017 , pp. 433-457 More about this Journal
Abstract
As a novel typical wind-sensitive structure, the wind load and wind-induced structural behaviors of super-large straight-cone cooling towers are in an urgent need to be addressed and studied. A super large straight-cone steel cooling tower (189 m high, the highest in Asia) that is under construction in Shanxi Power Plant in China was taken as an example, for which four finite element models corresponding to four structural types: the main drum; main drum + stiffening rings; main drum + stiffening rings + auxiliary rings (auxiliary rings are hinged with the main drum and the ground respectively); and main drum + stiffening rings + auxiliary rings (auxiliary rings are fixed onto the main drum and the ground respectively), were established to compare and analyze the dynamic properties and force transferring paths of different models. After that, CFD method was used to conduct numerical simulation of flow field and mean wind load around the cooling tower. Through field measurements and wind tunnel tests at home and abroad, the reliability of using CFD method for numerical simulation was confirmed. On the basis of this, the surface flow and trail characteristics of the tower at different heights were derived and the wind pressure distribution curves for the internal and external surfaces at different heights of the tower were studied. Finally, based on the calculation results of wind-induced responses of the four models, the effects of stiffening rings, auxiliary rings, and different connecting modes on the dynamic properties and wind-induced responses of the tower structure were derived and analyzed; meanwhile, the effect mechanism of internal suction on such kind of cooling tower was discussed. The study results could provide references to the structure selection and wind resistance design of such type of steel cooling towers.
Keywords
steel cooling tower; straight-cone type; numerical simulation; mean wind load; wind-induced response; internal pressure effect;
Citations & Related Records
Times Cited By KSCI : 6  (Citation Analysis)
연도 인용수 순위
1 Babu, G.R., Rajan, S.S., Harikrishna, P., Lakshmanan, N. and Arunachalam, S. (2013), "Experimental determination of wind-Induced response on a model of natural draught cooling tower", Exp. Techniques, 37(1), 35-46.   DOI
2 Baillis, C., Jullien, J.F. and Limam, A. (2000), "An enriched 2D modelling of cooling towers.: Effects of real damage on the stability under self-weight and on the strength under wind pressure", Eng. Struct., 22(7), 831-846.   DOI
3 BS4485 (Part 4) (1996), "Code of practice for structural design and construction-water cooling tower", London: British Standard Institution.
4 Busch, D., Harte, R., Kratzig, W.B. and Montag, U. (2002), "New natural draught cooling tower of 200 mheight", Eng. Struct., 24(12), 1509-21.   DOI
5 Cheng, X.X., Zhao, L., Ge, Y.J., Ke S.T. and Liu X.P. (2015), "Wind pressures on a large cooling tower", Adv. Struct. Eng., 18(2), 201-220.   DOI
6 DL/T 5339-2006 (2006), "Code for hydraulic design of fossil fuel power plants", The Ministry of Construction of China, Beijing: China , 115-116. (in Chinese)
7 Du, L.Y. and Ke, S.T. (2017), "Research on effect of internal pressures for super large cylinder-conic section steel cooling towers", The Journal of Central South University, accepted but not published. (in Chinese)
8 GB50009-2012 (2012), "Load code for the design of building structures", The Ministry of Construction of China, Beijing, China, 35-36. (in Chinese)
9 Goodarzi, M. (2010), "A proposed stack configuration for dry cooling tower to improve cooling efficiency under cross wind", J. Wind Eng. Ind. Aerod., 98(12), 858-863.   DOI
10 Izadi, M. and Bargi, K. (2014), "Natural draft steel hyperbolic cooling towers: Optimization and performance evaluation", Struct. Des. Tall Spec. Build., 23, 713-720.   DOI
11 Jeong, S.H. (2004), "Simulation of large wind pressures by gusts on a bluff structure", Wind Struct., 7(5), 333-344.   DOI
12 Ke, S.T., Ge, Y.J. and Zhao, L. (2015), "Wind-induced vibration characteristics and parametric analysis of large hyperbolic cooling towers with different feature sizes", Struct. Eng. Mech., 4(5), 891-908.
13 Ke, S.T., Ge, Y.J., Zhao, L. and Tamura Y. (2012), "A new methodology for analysis of equivalent static wind loads on super-large cooling towers", J. Wind Eng. Ind. Aerod., 111(3), 30-39.   DOI
14 Ke, S.T., Ge, Y.J., Zhao, L. and Tamura, Y. (2013), "Wind-induced Responses Characteristics on Super-large Cooling Towers", J. Central South Univ. Technol., 20(11), 3216-3227.   DOI
15 Shimaoka, S., Nakazawa, S., Kato, S., Shibata, R. and Okada, H. (2005), "A study on optimal parameters for buckling restrained members of steel cooling tower: Application of grid computing system", Summaries of technical papers of Annual Meeting Architectural Institute of Japan. B-1, Structures I, Loads, reliability stress analyses foundation structures shell structures, space frames and membrane structures. Architectural Institute of Japan, 847-848.
16 Ke, S.T., Liang, J., Zhao, L. and Ge, Y.J. (2015), "Influence of ventilation rate on the aerodynamic interference for two IDCTs by CFD", Wind Struct., 20(3), 449-468.   DOI
17 Li, L.X., Kareem, A., Xiao, Y.Q. and Zhou, C. (2015), "A comparative study of field measurements of the turbulence characteristics of typhoon and hurricane winds", J. Wind Eng. Ind. Aerod., 140, 49-66.   DOI
18 Niemann, H.J. and Kopper, H.D. (1998), "Influence of adjacent buildings on wind effects on cooling towers", Eng. Struct., 20(10), 874-880.   DOI
19 Stanislaw, H., Katarzyna, K. and Janina, F. (2016), "Acidity of vapor plume from cooling tower mixed with flue gases emitted from coal-fired power plant", Sci. Total Environ., 554, 253-258.
20 VGB-R610Ue (2005), "VGB-Guideline: structural design of cooling tower-technical guideline for the structural design, computation and execution of cooling towers", Essen: BTR Bautechnik Bei Kuhlturmen.
21 Viladkar, M.N., Karisiddappa, Bhargava, P. and Godbole, P.N. (2006), "Static soil-structure interaction response of hyperbolic cooling towers to symmetrical wind loads", Eng. Struct., 28(9), 1236-1251.   DOI
22 Wang, H., Tao, T.Y. and Wu, T. (2016), "Wind power spectra for coastal area of East Jiangsu Province based on SHMS", Wind Struct., 22(2), 235-252.   DOI
23 Zhao, L. and Ge, Y.J. (2010), "Wind Loading Characteristics of super-large cooling towers", Wind Struct., 13(4), 257-274.   DOI
24 Wittek, U. and Grote, K. (2015), "Substitute wind concept for elastic stability of cooling tower shells", Mater. Member Behavior, 500-513.
25 Zhang, J.F., Chen, H., Ge, Y.J., Zhao, L. and Ke, S.T. (2014), "Effects of stiffening rings on the dynamic properties of hyperboloidal cooling towers", Struct. Eng. Mech., 49(5), 619-629.   DOI