Abstract
In the present study, we developed optimal heat supply algorithm which minimizes the heat loss through the distribution pipe line in group energy apartment. Heating load variation of group energy apartment building in accordance with outdoor air temperature was predicted by the correlation obtained from calorimeter measurements of whole households of apartment building. Supply water temperature and mass flow rate were conjugately controlled to minimize the heat loss rate through distribution pipe line. Group heating apartment located in Hwaseong city, Korea, which has 1,473 households divided in 4 regions, was selected as the object apartment for verifying the present heat supply control algorithm. Compared to the original heat supply system, 10.4% heat loss rate reduction can be accomplished by employing the present control algorithm.
Keywords
Group energy; District heating; Optimal control; Heat loss; Heating load; Supply water; Heat supply; Household;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Choi, J.M., Lee, K.N., Ryu, S.R., Kim, Y.Y., Yeo, M.S and Kim, K.W., "A Study on the required supply water temperature calculating method for the control of multizone radiant floor heating system", Korea J. of Air-Conditioning and Refrigeration Engineers, 19(1) pp. 77-85, 2007.
2 Byun, J.K., Lee, K.H., Choi, Y.D. and Shin, J.K., "Analytic study on development of optimal heat supply control algorithm through heat load prediction in group energy apartment building variation of outdoor air temperature", Proceedings of the SAREK, pp. 666-671, 2010.
3 ASHRAE HANDBOOK 1993 Fundamentals, pp. 9-11, 1993.