Abstract
Leak detection is one of the most important challenges in condition monitoring of water pipelines. Fiber Bragg grating (FBG) sensors offer an attractive technique to detect leak signals. In this paper, leak measurements were conducted on a water distribution pilot plant with a length of 270 m and a diameter of 100 mm. FBG sensors were installed on the pipeline surface and used to detect leak vibration signals. The leak was demonstrated with 1-, 2-, 3-, and 4-mm diameter leak holes in four different pipe types. The frequency response of leak signals was analyzed by fast Fourier transform analysis in real time. In the experiment, the frequency range of leak signals was approximately 340-440 Hz. The frequency shifts of leak signals according to the pipe type and the size of the leak hole were demonstrated at a pressure of 1.8 bar and a flow rate of 25.51 m3/h. Results show that frequency shifts detected by FBG sensors can be used to detect leaks in pipelines.
Keywords
Fiber Bragg grating; Leak; Pipeline; Vibration; Water distribution network;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 J. M. Muggleton, M. J. Brennan, and R. J. Pinnington, "Wavenumber prediction of waves in buried pipes for water leak detection," J. Sound Vib. 249, 939-954 (2002).   DOI
2 Ministry of Environment, "Korean design standards of water treatment facility," KC Code KDS 57 55 00 (2017).
3 K. Ibrahim, S. Tariq, B. Bakhtawar, and T. Zayed, "Application of fiber optics in water distribution networks for leak detection and localization: a mixed methodology-based review," H2Open J. 4, 244-261 (2021).   DOI
4 H. Kim, S. Park, C. Yeo, H. S. Kang, and H.-J. Park, "Thermal analysis of 22.9-kV crosslinked polyethylene cable joint based on partial discharge using fiber Bragg grating sensors," Opt. Eng. 60, 034101 (2021).
5 D. Feng, X. Qiao, H. Yang, Q. Rong, R. Wang, Y. Du, M. Hu, and Z. Feng, "A fiber Bragg grating accelerometer based on a hybridization of cantilever beam," IEEE Sens. J. 15, 1532-1537 (2015).   DOI
6 S. Moore, "A review of noise and vibration in fluid-filled pipe systems," in Proc. 2nd Australasian Acoustical Societies Conference-ACOUSTICS (Brisbane, Australia, Nov. 9-11, 2016), pp. 701-710.
7 T. K. Chan, C. S. Chin, and X. H. Zhong, "Review of current technologies and proposed intelligent methodologies for water distributed network leakage detection," IEEE Access 6, 78846-78867 (2018).   DOI
8 U. Sampath, D. Kim, H. Kim, and M. Song, "Polymer-coated FBG sensor for simultaneous temperature and strain monitoring in composite materials under cryogenic conditions," Appl. Opt. 57, 492-497 (2018).   DOI
9 D. Zaman, M. K. Tiwari, A. K. Gupta, and D. Sen, "A review of leakage detection strategies for pressurised pipeline in steady-state," Eng. Fail. Anal. 109, 104264 (2020).   DOI
10 M. I. M. Ismail, R. A. Dziyauddin, N. A. A. Salleh, F. Muhammad-Sukki, N. A. Bani, M. A. M. Izhar, and L. A. Latiff, "A review of vibration detection methods using accelerometer sensors for water pipeline leakage," IEEE Access 7, 51965-51981 (2019).   DOI
11 K. B. Adedeji, Y. Hamam, B. T. Abe, and A. M. Abu-Mahfouz, "Towards achieving a reliable leakage detection and localization algorithm for application in water piping networks: An overview," IEEE Access 5, 20272-20285 (2017).   DOI
12 J. M. Lopez-Higuera, L. R. Cobo, A. Q. Incera, and A. Cobo, "Fiber optic sensors in structural health monitoring," J. Lightwave Technol. 29, 587-608 (2011).   DOI
13 P. Kumar, K. F. Fiaboe, and J. S. Roy, "Design of nonlinear photonic crystal fibers with ultra-flattened zero dispersion for supercontinuum generation," ETRI J. 42, 282-291 (2020).   DOI
14 D. Kim, H. Kim, and M. Song, "FBG laser sensor with PS," Electron. Lett. 54, 844-846 (2018).   DOI
15 W. Li, T. Liu, and H. Xiang, "Leakage detection of water pipelines based on active thermometry and FBG based quasi-distributed fiber optic temperature sensing," J. Intell. Mater. Syst. Struct. 32, 1744-1755 (2021).   DOI
16 K. Jiang, L. Liang, C. Hu, and X. Liu, "Fiber Bragg grating accelerometer-based nonintrusive flow rate measurements and leak detection," Appl. Opt. 59, 10680-10687 (2020).   DOI