Increasing Hosting Capacity of Distribution Feeders by Analysis of Generation and Consumption  

Kim, Seong-Man (Korea Electric Power Corporation)
Publication Information
KEPCO Journal on Electric Power and Energy / v.5, no.4, 2019 , pp. 295-309 More about this Journal
Abstract
This paper demonstrates that the verification and analysis of the increase of hosting capacity of distributed energy resources in distribution system for the high penetration of distributed energy resources. In the case of generally designed distribution feeders in South Korea, it can host up to 10 MVA of distributed energy resources and the over voltage due to reverse power flow is prohibited beyond the range by the law of electric utility. However, it should take into consideration that there are some factors of extra hosting capacity such as generation characteristics of distributed energy resources and minimum loads that always exist to distribution system. For these reason, we choose a specific distribution system hosted 10 MVA of distributed energy resources monitored by distribution system operator and verify the impact of increasing hosting capacity such as power flow and voltage profile of distribution system. By the result, we could find that it is possible to increase the hosting capacity and define the factors to expand the hosting capacity of distributed energy resources in distribution system.
Keywords
Hosting Capacity; DER; Distributed Energy Resources; Distributed Generation; PV; Distribution System; DER-Interconnection;
Citations & Related Records
연도 인용수 순위
  • Reference
1 제8차 전력수급기본계획, 산업통상자원부, 2017.
2 송배전용전기설비이용규정, 한국전력공사, 2019.
3 제3차 에너지기본계획, 산업통상자원부, 2019.
4 전기사업법, 산업통상자원부, 2019.
5 분산형전원 배전계통 연계 기술기준, 한국전력공사, 2018.
6 Youngbeom Jung, Byung-sung Lee, "Development of assessment algorithm for operating capacity on Distribution line using System Information," Fall Conference for Society Electrical Facility of KIEE, pp.47, Oct, 2013.