Browse > Article
http://dx.doi.org/10.18770/KEPCO.2019.05.04.263

Evaluation of Insulation Deterioration for the Development of SVM Algorithm to Diagnose OF Cable  

Kwak, Byeong Sub (KEPCO Research Institute, Korea Electric Power Corporation)
Jun, Tae-Hyun (KEPCO Research Institute, Korea Electric Power Corporation)
Kim, Ah-Reum (KEPCO Research Institute, Korea Electric Power Corporation)
Park, Hyun-joo (KEPCO Research Institute, Korea Electric Power Corporation)
Publication Information
KEPCO Journal on Electric Power and Energy / v.5, no.4, 2019 , pp. 263-273 More about this Journal
Abstract
South Korea's OF cable is reaching its expected design life of 30 years, and as a result, the risk of failure is increasing. Therefore, it is necessary to diagnose the long-term operating OF cables through accurate diagnosis at the right time to prevent the failure. Currently, the KEPCO periodically conducts DGA. However, the gas found in DGA is caused by oil deterioration as well as insulation paper. Therefore, the analysis of the degree of polymerization and furan compounds which is an evaluation of insulation paper considered to be the life of OF cables is required. In addition, the results of the evaluation of deterioration of insulation paper need to be checked for correlation with the results of DGA. In this study, DGA carried out through GC, the degree of polymerization was analyzed using an automatic viscometer, and HPLC was used to detect the furan compounds. In addition, the obtained results were applied to the SVM technique, which was recently introduced to determine abnormalities in OF cable. And the results which were accurate and reliable were obtained.
Keywords
OF Cable; Underground Transmission Line; DGA; SVM; Degree of Polymerizations;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Chatterjee, A., Bhattacharjee, P., Roy, N.K., Kumbhakar, P., "Usage of nanotechnology-based gas sensor for health assessment and maintenance of transformers by DGA method," Electrical Power and Energy Systems, 45(2013), pp.137-141, October, 2012.
2 Fofana, I., Hemmatjou, H., Farzaneh, M., "Low temperature and moisture effects on polarization and depolarization currents of oil-paper insulation," Electric Power Systems Research, 80(2010), pp.91-97, September, 2009.
3 Jiangjun, R., Shuo, J., Zhiye, D., Yiming, X., Lin, Z., Yu, T., Ruohan, G., Guannan, L., Min, X., "Condition Assessment of Paper Insulation in Oil-Immersed Power Transformers Based on the Iterative Inversion of Resistivity," Energies, 10. pp.509-523, April, 2017.   DOI
4 Polansky, R., Prosr, P., Vik, R., Moravcova, D., Pihera, J., "Comparison of the mineral oil lifetime estiates obtained by differential scanning calorimetry, infrared spectroscopy, and dielectric dissipation factor measurements," Thermochimica Acta, 647(2017), pp.86-98, December, 2016.
5 Adekoya, D., Adejumobi, I., "Analysis of acidic properties of distribution transformer oil insulation: a case study of Jericho(Nigeria) distribution network," Nigerian Journal of Technology, 36(2), pp.563-570, April, 2017.   DOI
6 Jong-Chul Lee., Hyeon-Seok S., Youn-Jea K., "The increased dielectric breakdown voltage of transformer oil-based nanofluids by an external magnetic field," International Journal of Thermal Sciences, 62(2012), pp.29-33, April, 2012.   DOI
7 Darabad, V., Vakilian, M., Blackburn, T., Phung, B., "An efficient PD data mining method for power transformer defect models using SOM technique," Electrical Power and Energy Systems, 71(2015), pp.373-382, March, 2015.   DOI
8 전기협동연구 "지중송전케이블의 보전기술" 제70권 1호
9 Hill, D.J.T., Le, T.T., Darveniza, M., Saha, T., "A study of degradation of cellulosic insulation materials in a power transformer. Part 2: tensile strength of cellulose insulation paper," Polymer Degradation and Stability, 49(1995), pp.429-435, June, 1995.   DOI
10 Hanung, N.S., Suwarno, Nanang, H., Yoshinobu, M., Tsuguhiro, T., Tatsuki, O., "Degree of Polymerization Estimation of Insulation Papers in Power Transformers Based on Load and Temperature Histories in Java-Bali Region of Indonesia National Electric Company," IEEE, 2012, pp.23-27.
11 Pahlavapour, B., Eklund, M., Martins, M., "Insulating Paper Ageing and Furfural Formation," IEEE, 2003, pp.283-288.
12 Katsunori, M., Etsuo, O., Naoki, Y., "Evaluation of Aging for Thermally Upgraded Paper in Mineral Oil," Journal of International Council on Electrical Engineering," 1(2), pp.181-187, March, 2011.   DOI