Suppression of Common-Mode Voltage in a Multi-Central Large-Scale PV Generation Systems for Medium-Voltage Grid Connection  

Bae, Young-Sang (Dept. of Electrical Eng., EECS Lab, Hanyang University)
Kim, Rae-Young (Dept. of Electrical and Biomedical Eng., Hanyang University)
Publication Information
The Transactions of the Korean Institute of Power Electronics / v.19, no.1, 2014 , pp. 31-40 More about this Journal
Abstract
This paper describes an optimal configuration for multi-central inverters in a medium-voltage (MV) grid, which is suitable for large-scale photovoltaic (PV) power plants. We theoretically analyze a proposed common-mode equivalent model for problems associated with multi-central transformerless-type three-phase full bridge(3-FB) PV inverters employing two-winding MV transformers. We propose a synchronized PWM control strategy to effectively reduce the common-mode voltages that may simultaneously occur. In addition, we propose that the existing 3-FB topology may also have the configuration of a multi-central inverter with a two-winding MV transformer by making a simple circuit modification. Simulation and experimental results of three 350kW PV inverters in a multi-central configuration verify the effectiveness of the proposed synchronization control strategy. The modified transformerless-type 3-FB topology for a multi-central PV inverter configuration is verified using an experimental prototype of a 100kW PV inverter.
Keywords
central inverter; medium voltage; common mode; leakage current;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 World Wide Fund for Nature (WWF), ECOFYS and OMA, "The energy report: 100% renewable energy by 2050," Gland, Switzerland, Jan. 2011.
2 RENI, "Renewables insight energy industry guides," Solarpraxis, Berlin, 2011.
3 B. Yang, W. Li, Y. Gu, W. Cui, X. He, "Improved transformerless inverter with common-mode leakage current elimination for a photovoltaic grid-connected power system," IEEE Transactions on Power Electronics, Vol. 27, No. 2, pp. 752-762, Feb. 2012.   DOI   ScienceOn
4 O. Lopez, R. Teodorescu, F. Freijedo, J. Doval-Gandoy, "Leakage current evaluation of a single-phase transformerless PV inverter connected to the grid," in Proc. IEEE of APEC'07, pp. 907-912, 2007.
5 S.V. Araujo, P. Zacharias, R. Mallwitz, "Highly efficient single-phase transformerless inverters for grid-connected photovoltaic systems," IEEE Transactions on Industrial Electronics, Vol. 57, No. 9, pp. 3118-3128, Sept. 2010.   DOI   ScienceOn
6 O. Lopez, R. Teodorescu, F. Freijedo, J. Doval-Gandoy, "Eliminating ground current in a transformerless photovoltaic application," IEEE Transactions on Energy Conversion, Vol. 25, No. 1, pp. 140-147, Mar. 2010.   DOI   ScienceOn
7 M. C. Cavalcanti, P. E. P. Ferraz, F. A. S. Neves, E. C. dos Santos, J. H. G. M. da Silva, "Modulation for three-phase transformerless z-source inverter to reduce leakage currents in photovoltaic systems," IEEE Transactions on Industrial Electronics, Vol. 58, No. 12, pp. 5385-5395, Dec. 2011.   DOI
8 X. Wang, F. Zhuo, J. Li, L. Wang, S. Ni, "Modeling and control of dual-stage high-power multifunctional PV system in d-q-o coordinate," IEEE Transactions on Industrial Electronics, Vol. 60, No. 4, pp. 1556-1570, Apr. 2013.   DOI   ScienceOn
9 B. Gu, J. Dominic, J.-S. Lai, C.-L. Chen, T. LaBella, B. Chen, "High reliability and efficiency single-phase transformerless inverter for grid-connected photovoltaic systems," IEEE Transactions on Power Electronics, Vol. 28, No. 5, pp. 2235-2245, May 2013.   DOI
10 S. B. Kjaer, J. K. Pedersen, F. Blaabjerg, "A review of single-phase grid-connected inverters for photovoltaic modules," IEEE Transactions on Industry Applications, Vol. 41, No. 5, pp. 1292-1306, Sep. 2005.   DOI   ScienceOn
11 R. Araneo, S. Lammens, M. Grossi, S. Bertone, "EMC issues in high-power grid-connected photovoltaic plants," IEEE Transactions on Electromagnetic Compatibility, Vol. 51, No. 3, pp. 639-648, Aug. 2009.   DOI
12 J.-P. Lee, B.-D. Min, D.-W. Yoo, "Implementation of a High Efficiency Grid-Tied Multi-level Photovoltaic Power Conditioning System Using Phase Shifted H-Bridge Modules," Journal of Power Electronics, Vol. 13, No. 2, pp. 296-303, Mar. 2013.   과학기술학회마을   DOI
13 T. Kerekes, R. Teodorescu, M. Liserre, "Evaluation of three-phase transformerless photovoltaic inverter topologies," IEEE Transactions on Power Electronics, Vol. 24, No. 9, pp. 2202-2211, Sep. 2009.   DOI
14 T. Kerekes, R. Teodorescu, M. Liserre, "Common mode voltage in case of transformerless PV inverters connected to the grid," IEEE International Symposium on Industrial Electronics, pp. 2390-2395, Jun./July 2009.
15 R. Gonzalez, E. Gubia, J. Lopez, L. Marroyo, "Transformerless single-phase multilevel-based photovoltaic inverter," IEEE Transactions on Industrial Electronics, Vol. 55, No. 7, pp. 2694-2702, July 2008.   DOI   ScienceOn
16 DKE Deutsche Kommission Elektrotechnik Elektronik Informationstechnik im DIN und VDE, DIN VDE 0126-1-1, Paragraph 4.7.1. Photovoltaik, 2006.
17 Texas Instruments, "TMS320x2834x Delfino Enhanced Controller Area Network (eCAN)," reference guide, Mar. 2009.
18 Texas Instruments, "TMS320x2834x Delfino Enhanced Pulse Width Modulator (ePWM) Module," reference guide, Sep. 2009.
19 H. Chen, J. Tian, "Research on the controller area network," International Conference on Networking and Digital Society, Vol. 2, pp. 251-254, May 2009.
20 Y. Wang, R. Li, "Novel high-efficiency three-level stacked-neutral-point-clamped grid-tied Inverter," IEEE Transactions on Industrial Electronics, Vol. 60, No. 9, pp. 3766-3774, Sep. 2013.   DOI
21 H. W. Ping, N. A. Rahim, J. Jamaludin, "New Three-Phase Multilevel Inverter with Shared Power Switches," Journal of Power Electronics, Vol. 13, No. 5, pp. 787-797, Sep. 2013.   DOI
22 M. Cavalcanti, A. Farias, K. Oliveira, F. Neves, "Eliminating leakage currents in neutral point clamped inverters for photovoltaic systems," IEEE Transactions on Industrial Electronics, Vol. 59, No. 1, pp. 435-443, Jan. 2012.   DOI