Browse > Article

The Analysis and Adjustment for the Control Parameter of HVDC System  

Kim, Chan-Ki (한전 전력연구원)
Publication Information
The Transactions of the Korean Institute of Power Electronics / v.11, no.2, 2006 , pp. 184-191 More about this Journal
Abstract
This paper deals with the HVDC system fault analysis and the tuning of the control parameter. This paper is based on the actual cable fault which was caused by the overvoltage due to commutation failure. In order to analyze the fault, the detailed PSCAD/EMTDC model which the sampling time is $50{\mu}s$, was made. Finally, the control parameter of HVDC system was tuned.
Keywords
HVDC; HVDC Model; Fault Analysis;
Citations & Related Records
연도 인용수 순위
  • Reference
1 T. Jonnson and P.Bjorklund, 'Capacitor Commutated Converters for HVDC' Stockholm PowerTech, June 1995, Proceedings: Power Electronics, pp 44-51
2 J. Vithayathil, 'Converter Terminals Connected to Weak Ac System-Reactive Power Compensation, Control Strategies and Application of Static Var Systems', Proc. Intl. Symposium of HVDC Technology Rio de Janeiro, Part II, March 1983, pp. 69-70
3 T. Jonsson, P-E. Bjorklund, 'Capacitor Commutated Converters for HVDC,' Stockholm power Tech. Conference, Stockholm, June 1995, pp.44-51
4 A.M. Gole and R.W. Menzies, 'Analysis of Certain Aspects of Forced Commutated HVDC Inverters', IEEE Trans. PAS, Vol. PAS-100, No. 5, May 1981, pp. 2258-2262   DOI
5 H.M Turanli and R.W. Menzies, 'Feasibility of DC Transmission with Forced Commutation to Remote Loads', IEEE Trans. Power Apparatus and Systems, Vol. 103, No. 6, June 1984, pp. 1256-1262   DOI   ScienceOn
6 M.O.Faruque etc, 'Algorithms for the according of multiple switching events in digital simulation of power electronics systems', IEEE Trans. on power Delivery, Vol. 20, No. 2 April, 2005, pp. 1157-1167   DOI   ScienceOn
7 Chris Osauskas etc, 'Small Signal Dynamic Modeling of HVDC System', IEEE Trans. on Power Delivery, Vol. 18, No. 1 Jan. 2003, pp.220-pp225   DOI   ScienceOn