Browse > Article

Firing Angle Control of Soft Starter for Reduction of Inrush Current during Grid Connection of Induction-type Wind Generator  

Song Seung-Ho (전북대 전자정보공학부)
Kwon Tae-Hwa ((주)져스텍)
Publication Information
The Transactions of the Korean Institute of Power Electronics / v.10, no.4, 2005 , pp. 397-402 More about this Journal
Abstract
A new control algorithm of soft starter is proposed for the reduction of the inrush current during the grid connection of the induction-type wind power generator. Currently, the fixed speed wind turbine using induction generator is the most popular wind generation system in Korea. It is shown that the amount of inrush current mainly depends on the control algorithm of the soft starter, a thyristor-based grid connection device. For the simulation study, a 600kw wind turbine simulation model is developed and the transient waveforms are investigated with conventional md proposed methods. Also experimental results using 3.7kW experimental set-up show that the peak value of inrush current is reduced about 20$\%$ using proposed algorithm.
Keywords
Fixed Speed Wind Turbine; Induction Generator; Firing Control of Soft Starter;
Citations & Related Records
연도 인용수 순위
  • Reference
1 장성일, 정종찬, 최정환, 박제영, 김광호, '농형 풍력 발전기의 운전 특성에 관한 연구', 대한전기학회 하계학술대회 B권, pp. 1309-1312, 2002
2 V44 System Manual, Vestas, 1999
3 정병창, 정세종, 송승호, '가변관성 모의 기능을 가진 풍력터빈 시뮬레이터의 제어 알고리즘', 전력전자학회 논문지, Vol. 8, No.3, pp. 266-273, 2003
4 Paresh C. Sen, 'Principles of Electric Machines and Power Electronics', p.231. 1998
5 윤기갑, 이완수, 김병한, 이상길, '울릉도 풍력발전 계통 연계 문제점 및 대책', 대한전기학회 EMECS학회 추계 학술대회, pp. 305-307, 2001
6 G. Zenginobuz, I. Cadirci, M. Ermis, C. Barlak, 'Soft Starting of Large Induction Motors at Constant Current With Minimized Starting Torque Pulsations' IEEE Trans. on Industry Applications VoI37. No5, pp 1334-1347, 2001   DOI   ScienceOn
7 전영진, 김일환, '제주 행원 풍력발전 시스템의 모델링 및 해석' 전력전자 하계학술대회, pp. 563-566, 2002