A Study on the Performance Evaluation of Combined Heat Pump System according to the Ratio of Ground Heat Source and Water Heat Source  

Park, Sihun (Department of Mechanical Engineering, KyungHee University)
Ko, Yujin (Department of Mechanical Engineering, KyungHee University)
Min, Joonki (Department of Mechanical Engineering, KyungHee University)
Publication Information
Journal of the Korean Society for Geothermal and Hydrothermal Energy / v.17, no.2, 2021 , pp. 11-19 More about this Journal
Abstract
In this study, combined heat source heat pump system was implemented with 4 single heat source heat pumps each applied with a geothermal source and a water source. Five cases (Case1~Case5) were configured to conduct a performance comparison and analysis of the combined heat source heat pump system. First of all, as a result of analyzing the heat source, the case when 4 ground heat sources were applied (Case1) showed a uniform EST(Entering Source Temperature) distribution throughout the year since it is less affected by outside air compared to the case when 4 water heat sources were applied (Case5). In both winter and summer, the ground heat source maintained higher EST than the water heat source. Therefore, the system with high ratio of geothermal sources is advantageous for heating, and with high ratio of water heat sources is advantageous for cooling.
Keywords
Ground heat source; Water heat source; Combined heat source; Heat pump; COP(Coefficient Of Performance);
Citations & Related Records
연도 인용수 순위
  • Reference
1 Bae, H. H., Lee, D. H., Lee, S., Kim, B., and Ahn, Y. C., A Study on the Performance Improvement of a Simultaneous Heating and Cooling Water Source Heat Pump System by Controlling of the Refrigerant Flow Rate in an Outdoor Unit, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 25, No. 3, pp. 131-136.   DOI
2 Sohn, B., Design of Ground-Coupled Heat Pump (GCHP) System and Analysis of Ground Source Temperature Variation for School Building, Korea Society of Geothermal Energy Engineers, Vol. 16, No. 1, pp. 17-25.
3 Ko, Y., Park, S., and Min, J., Comparison of Heat Pump Performance and Energy Consumption Patterns according to Heat Sources for Optimal Control of Multi-Source Heat Pumps, Korea Society of Geothermal Energy Engineers, Vol. 16, No. 4, pp. 31-38.
4 Cho, Y. U., Woo, T., Chung, K. S., and Kim, Y., Study on Energy Consumption of Air-source, Ground-source and Dual-source Heat Pump during Intermediate Season, Korea Society of Geothermal Energy Engineers, Vol. 9, No. 4, pp. 1-7.
5 Sohn, B., Lee, D. Y., Choi, J. H., and Min, K. C., Performance Analysis of Cooling Tower-Assisted Hybrid Ground-Coupled Heat Pump (HGCHP) System, Trans. Korean Soc. Mech. Eng. C, Vol. 4, No. 1, pp. 19-26.
6 Ministry of Land, Infrastructure and Transport, 2017, Standard of Building Saving, MLIT criteria 2017-881.
7 Klein, S. A., 2019, TRNSYS18 Base Manual, KESTech, Kocaeli, Turkey.
8 Bea, S., Jeon, J. Y., Kwon, Y. S., and Nam, Y., Study on the Operation Method of Ground Source Heat Pump System Considering Recovery of Ground Temperature, Korea Society of Geothermal Energy Engineers, Vol. 16, No. 4, pp. 24-30.