Abstract
Uniform laws and regulations and reasonable design is necessary for the prevention of possible fire in super high-rise building. To this end, this study focused on super high-rise and massive building-related architectural review performance-based design (PBD) evaluation disaster impact assessment (DIA), and provided fire engineering measures for improving fire prevention on the basis of performance-based design by analyzing the buildings subject to these systems and problems in terms of contents. Above all, in the aspect of law and standard improvement, first, with regard to dual parts of two statutes though significant portion of them has the same contents in performance-based design (PBD) evaluation and disaster impact assessment (DIA), it is necessary to operate the systems after making them conform with each other and consolidating or abolishing them. Second, if it is impossible to consolidate or abolish performance-based design (PBD) evaluation and disaster impact assessment (DIA), the areas of contents of performance-based design (PBD) evaluation and disaster impact assessment (DIA) should be precisely classified and established. Next, engineering improvement measures against fire hazard in super high-rise building are as follows. First, it is necessary to revise the provisions of straight-run stairs in special escape stairs. And in case of installing a mechanical smoke exhaust system instead of smoke vent, sandwich pressurization used in the United Stated should be permitted. Second, with regard to smoke control system for special escape stairs, it was shown that there was necessity for revising the standards in order to enable air to be supplied according to section in case of fire, carrying out performance-based design, and the like from the early design stages to the completion stages. In the future, it is expected that an epoch-making contribution will be made to a decrease in casualties and property damage due to fire in case of super high-rise building where the results can be reflected after carrying out a study on maintenance and carrying out an additional study on other considerations of super high-rise building together with reflecting the improvement measures provided in the above-mentioned study.
Keywords
High-rise buildings; Performance-Based Design; Disaster impact assessment; Sandwich pressure method; Evacuation floor; Evacuation stairs; Stack effect; Accreditation system; Risk assessment techniques; National Fire Information System;
Citations & Related Records
연도 인용수 순위
  • Reference
1 National Emergency Management Agency, (2014), "Special Act on the complex high-rise buildings and underground links Disaster Management", NEMA.
2 National Emergency Management Agency, (2015), "Fire Administration statistics 2015", NEMA.
3 NFPA, (2009), "NFPA 101 Life Safety Code", National Fire Protection Association.
4 Ministry of Public Safety and Security, (2015), Disaster Statistical Yearbook, MPSS, pp. 241-243.
5 J. P. Choi, B. J. Jang, Y. S. Park, Y. J, Lee, (2005), "Introduction of the concept evacuation floor and shelter space for high-rise building" Architectural Institute of Korea, Vol. 21, No. 3, pp. 147-154.
6 Municipal Development Institute, (2010), "Ensuring method of fire safety in high-rise buildings", pp. 193-194
7 H. S. Hwang, (2013), "Disaster prevention measures in high-rise buildings", Fire magazine, Vol. 1, pp. 19-24.
8 S. H. Choi, (2009), "Improvement method for ventilation equipment of high-rise building", Facilities Journal, Vol. 38, No. 11, pp. 26-33.
9 H. S. Hwang, (2009), "Complex high-rise building fire protection facilities design practices" , Facilities Technology Association of Korea, Vol. 26, No. 12, pp. 39-47.
10 J.Y. Kim, (2010), "Technology Status of ventilation facilities in high-rise buildings", Korea Institute of Construction Technology, Construction Technology Trends, pp. 34-35.
11 C. H. Choi, (2009), "Performance-Based Fire Protection Design Case in high-rise buildings", Facilities Technology Association of Korea, Vol. 26, No. 12, pp. 48-59.
12 J. S. Choi, (2011). "BIM application method of high-rise buildings" Ssangyong Institute of Construction Technology.
13 Y. D. Kim, (2007), "Disaster prevention facilities of high-rise building", Facilities Technology Association of Korea, Vol. 24, No. 1, pp. 79-86.
14 Y. J. Lee, (2014), "A Study on the Fire Safety Regulations for High Rise Buildings and Megastructure",Fire magazine, Vol. 2, pp. 58-67.
15 S. C. Lee, (2013), "Consideration for the Improvement of ventilation equipment in high-rise buildings", Fire magazine, Vol. 1, pp. 15-18.