Browse > Article
http://dx.doi.org/10.5207/JIEIE.2014.28.2.060

The Study of the Circulation Current Control Scheme on Single Phase Inverter System  

Lee, Woo-Cheol (Hankyong National University Dept. of Electrical Electronic & Control Engineering, Institute for information technology convergence)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.28, no.2, 2014 , pp. 60-69 More about this Journal
Abstract
This paper proposed the circulation current control scheme in the single phase inverter system. The load experiment of the power conversion system including the UPS usually uses the passive components such as resistors and inductors. Therefore, the energy consumption is serious problem. In addition, the system is out of order when it is installed in the local area, and the load experiment can not perform adequately after troubleshooting, because there is no the load equipment, and the power capacity is not enough in the local area. The paper does the research on the circulation current control scheme, it does not need the load equipment, and the load current can reuse as the input current of the equipment. Instead of the conventional method the voltage-voltage and voltage-current control scheme introduced the parallel converter concept is newly proposed, and the validity of the proposed control scheme is investigated by both simulation and experimental results.
Keywords
Circulation Current Control Scheme; Voltage-Voltage; Voltage-Current Control Scheme;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 Bekiarov. S.B., Nasiri. A., Emadi. A., "A New Reduced Parts On-Line Single-Phase UPS System", Industrial Electronics Society, IECON '03. The 29th Annual Conference of the IEEE, vol. 1, pp. 688-693, 2003.
2 H. S. Kim, J.H. Han, J.H. Song, "Parallel Operation of Three-Phase Four wire UPS using Droop Control", Journal of the Korean Institute of Illuminating and Electrical Installation Engineers, Vol. 27, No. 4, pp. 88-95, Apr. 2013.   과학기술학회마을   DOI
3 W. C. Lee, D. S. Yoo, "Study on DC Charging Algorithm of the Line‐Interactive UPS with Dual Converter Structure", Journal of the Korean Institute of Illuminating and Electrical Installation Engineers, Vol. 19, No. 3, pp. 27-34 May, 2005.   과학기술학회마을   DOI   ScienceOn
4 W. C. Lee, T. K. Lee, "A Design of a High Performance UPS with Capacitor Current Feedback for Nonlinear Loads", Journal of the Korean Institute of Illuminating and Electrical Installation Engineers, Vol. 26, No. 5, pp. 71-78 May, 2012.   과학기술학회마을   DOI   ScienceOn
5 H. Cha, S. Lee, T. Vu "A new fast peak detector for single or three-phase unsymmetrical voltage sags", Energy Conversion Congress and Exposition (ECCE), 12-16 Sept. 2010, pp.434 - 440.
6 Jiann-Fuh Chen, Ching-Lung Chu, Tsu-Hua Ai, Ching-Lien Huang, "The burn-in test of three-phase ups by energy feedback method", Power Electronics Specialists Conference, pp. 766-771, 1993.
7 Suresh Gupta, Vidya Rangaswamy, "Load bank elimination for ups testing", Industry Applications Society Annual Meeting, vol. 2, pp. 1040-1043, 1990.
8 Chu, C.L, Chen, J.F , "Self-load bank for UPS testing by circulating current method", Electric Power Applications, IEE Proceedings, vol. 141, pp. 191-196, 1994.   DOI