Browse > Article
http://dx.doi.org/10.5207/JIEIE.2012.26.2.051

An Improved Method for Fault Location based on Traveling Wave and Wavelet Transform in Overhead Transmission Lines  

Kim, Sung-Duck (Department of Electronic Engineering, Hanbat National University)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.26, no.2, 2012 , pp. 51-60 More about this Journal
Abstract
An improved method for detecting fault distance in overhead transmission lines is described in this paper. Based on single-ended measurement, propagation theory of traveling waves together with the wavelet transform technique is used. In estimating fault location, a simple, but fundamental method using the time difference between the two consecutive peaks of transient signals is considered; however, a new method to enhance measurement sensitivity and its accuracy is sought. The algorithm is developed based on the lattice diagram for traveling waves. Representing both the ground mode and alpha mode of traveling waves, in a lattice diagram, several relationships to enhance recognition rate or estimation accuracy for fault location can be found. For various cases with fault types, fault locations, and fault inception angles, fault resistances are examined using the proposed algorithm on a typical transmission line configuration. As a result, it is shown that the proposed system can be used effectively to detect fault distance.
Keywords
Fault Location; Lattice Diagram; Modal Transformation; Overhead Transmission Line; Traveling Wave; Wavelet Transform;
Citations & Related Records
연도 인용수 순위
  • Reference
1 A. Elhaffar and M. Lehtonen, "Travelling waves based earth fault location in 400[kV] transmission network using single end measurement", 2004 Large Engineering Systems Conference on Power Engineering, LESCOPE-04, pp. 53-56, Westin Nova, Scotian, July, 2004.
2 A. Elhaffar, Power Transmission Line Fault Location Based On Current Traveling Waves, Ph.D. Thesis, Helsinki University of Technology, 2008.
3 M.L. Jacobson, "Auto-threshold peak detection in physiological signals", Proceedings of the 23rd Annual International Conference of the IEEE, Engineering in Medicine and Biology Society, vol. 3, pp. 2194-2195, 2001.
4 Y.J. Shin, E.J. Powers, W. M. Grady and S.C. Bhatt, "Effects of dispersion on disturbance propagation on high voltage transmission lines", IEEE Power Engineering Society Summer Meeting, vol. 2, pp. 851-854, Seattle, WA, USA, 2000.
5 IEEE Std., C37.114TM - 2004, IEEE Guide for Determining Fault Location on AC Transmission and Distribution Lines, IEEE Power Engineering Society, New York, Jun. 2005.
6 S.L. Zimath, C.A. Dutra and C. Seibel, "Comparison of impedance and traveling wave methods of fault location using real faults", Fault & Disturbance Analysis Conference, Atlanta, GA, USA, April 20-21, 2009.
7 F.H. Magnago and A. Abur, "Fault location using wavelets", IEEE Trans. on Power Delivery, vol. 13, no. 4, pp. 1475-1480, 1998.   DOI