Experimental Study of The Floating-Phenomenon on Neutral Ungrounded UPS System  

Shim, Hae-Sup (기상청 국가기상위성센터)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.25, no.5, 2011 , pp. 67-72 More about this Journal
Abstract
In this study we investigate the background of UPS output transformer(${\Delta}-Y$) operation on neutral ungrounded system, and perform field experiment of neutral floating-phenomenon for the inter-locked securing of electric facilities and improvement of neutral floating-phenomenon. Experiment results show that a floating-phenomenon occurs when four-pole input-breaker trip and the neutral to earth voltage occurring concurrently is identified as phantom voltage. And the measures for the transient overvoltage that can occur in floating-state also are investigated. As a result, the risk elements of neutral ungrounded method as well as neutral floating-phenomenon are removed by installation of separate solidly-grounded transformer and switching four-pole input-breaker to three-pole input breaker.
Keywords
Neutral Floating-Phenomenon; Phantom Voltage; Transient Overvoltage;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Engineering Department Bulletin, “Phantom Voltages”, NEMA, No.88, 2003. 2.
2 Application Note, “Ghost Voltages”, FLUKE, 2003.
3 David Shipp, Frank Angelini, Characteristics of different power systems neutral grounding techniques : Fact & Fiction, IEEE 2008 Industry applications society technical conference.
4 “Green Book : System grounding for uninterruptible power system”, Institute of Electrical and Electronics Engineers(IEEE), pp 5-56, 2007.
5 S.N. Singh, “Electric power generation, transmission and distribution”, Prentice-Hall, pp 384-386, 2006.
6 “Emerald Book : Powering and grounding electronic equipment”, Institute of Electrical and Electronics Engineers(IEEE), pp 282-286, 2005.