Browse > Article
http://dx.doi.org/10.5207/JIEIE.2011.25.5.061

A Study on the Safety of Medical IT System connecting Medical Insulation Transformer in Medical Locations  

Kim, Se-Dong (두원공과대학)
Kim, Eun-Sik (대한전기협회 기술처)
Park, Jung-Il (국토해양부)
Choi, Hyung-Sik (대한전기협회 전문위)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.25, no.5, 2011 , pp. 61-66 More about this Journal
Abstract
An accidental disconnection of power supply for operating theatres may result in fatal accidents. Thus, it is necessary to import the electric safety system in medical locations. This paper shows an analysis of simulation for the safety in medical IT system based on KS C IEC 60364-7-710(Electrical Installations of Buildings - Requirements for special installations or locations - Medical locations). The analysis was progressed by measuring leakage currents according to variation of volts, circuits and loads. And it was made database for calculation the reasonable length of branch circuit.
Keywords
Medical IT System; Medical Locations; Leakage Experimental Test;
Citations & Related Records
연도 인용수 순위
  • Reference
1 KS C IEC 60364-7-710(건축전기설비-특수장소에 대한 요구사항-의료장소), 2005.
2 오청환, 김영배, ‘의료실의 배선 및 접지방식' 조명 및 전기설비학회지, No. 11, 2005.
3 지식경제부, 전기설비기술기준 및 판단기준, 2010.
4 김은식, 최형식 외, 병원전기설비에 관한 시설기준 설정 및 세부지침에 관한 연구, 지식경제부(대한전기협회), 2010.