Browse > Article
http://dx.doi.org/10.5207/JIEIE.2011.25.11.050

A Study on Boost Type Single-Phase Inverter System for Compensation of Voltage Sag  

Seo, Young-Min (단국대 대학원 전기공학과)
Lee, Seung-Yong (단국대학교 대학원 전자전기공학과)
Hong, Soon-Chan (단국대 전자전기공학부)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.25, no.11, 2011 , pp. 50-57 More about this Journal
Abstract
This paper proposes a boost type single-phase inverter system to compensate the voltage sag appeared on source side. The proposed system is composed of a boost converter, a PWM inverter, and a bypass diode. If the voltage sag has appeared in input voltage, the boost converter would be operated to compensate it in the proposed system. The boost converter would not be operated when the magnitude of input voltage is more than 0.9 pu. The output voltage is kept constant by a direct-quadrature frame controller in the inverter. A 300 W class boost type inverter system was simulated, and the validity of the proposed system was verified by carrying out experiments.
Keywords
Voltage Sag; Inverter; Boost Converter; Voltage Sag Compensation;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Mario Fabiano Alves and Tatiana Nesralla Ribeiro, "Voltage Sag : An Overview of IEC and IEEE Standards and Application Criteria", IEEE Transmission and Distribution Conference, Vol. 2, pp. 585-589, 1999.
2 Ding Ning, Cai Wei, Suo Juan, Wang Jianwei, and Xu Yonghai, "Voltage Sag Disturbance Detection Based on RMS Voltage Method", Asia Pacific Power and Energy Engineering Conference, pp. 1-4, 2009.
3 Jing Zhou, Hui Zhou, and Zhiping Qi, "The Study on a Dual-Feed-Forward Control of DVR to Mitigate the Impact of Voltage Sags Caused by Induction Motor Starting", International Conference on Electrical Machines and Systems, pp. 1497-1500, 2008.
4 IEC 61000-4-11:2008, Testing and Measurement Techniques - Voltage Dips, Short Interruptions and Voltage Variations Immunity Tests.
5 IEC 61000-2-4:2007, Environment-Compatibility Levels in Industrial Plants for Low-Frequency Conducted Disturbances.
6 IEEE std. 493-2007, IEEE Recommended Practice for the Design of Reliable Industrial and Commercial Power Systems.
7 SEMI F47-0706:2006, Specification for Semiconductor Processing Equipment Voltage Sag Immunity.
8 Daniel W. Hart, Power Electronics, McGraw-Hill, 2011.
9 R. Teodorescu, F. Blaabjerg, M. Liserre, and P. C. Loh, "Proportional-Resonant Controllers and Filters for Grid-Connected Voltage-Source Converters", IEE Proceedings - Electric Power Applications, Vol. 153 Issue 5, pp. 750-762, September 2006.   DOI   ScienceOn
10 Robert F. Coughlin and Frederick F. Driscoll, Operational Amplifiers and Linear Integrated Circuits, Prentice-Hall, Inc., 2001.
11 Richard Zhang, Mark Cardinal, Paul Szczesny, and Mark Dame, "A Grid Simulator with Control of Single-Phase Power Converters in D-Q Rotating Frame", Power Electronics Specialists Conference, Vol. 3, pp. 1431-1436, 2002.
12 IEEE Std. 1159-2009, IEEE Recommended Practice for Monitoring Electric Power Quality.