Abstract
We experiment to analyze on current limiting and recovery characteristics of trigger type SFCL as the composition of the contact. Generally, some superconductor of SFCL is relatively largely loaded due to limit the fault current by oneself and recovery time is affected until the fault cleared. However, in the fault, the proposal trigger type SFCL transfer the fault current to current limiting reactor(CLR) using power switch so it could reduce the recovery time and load of the superconductor. However, because of applying the additional power switches, that could generate some power loss. Therefore, to solve this problem, we proposed the composition method of the double contact for a trigger type SFCL and analyzed on current limiting and recovery characteristics for ones.
Keywords
Superconducting Fault Current Limiter (SFCL); Trigger; Recovery Characteristics;
Citations & Related Records
연도 인용수 순위
  • Reference
1 B. Gromoll, G. Ries, W. Schmidt, H.-P. Kraemer, B. Seebacher, B. Utz, R. Nies, and H.-W. Newmuller, "Resistive fault current limiter with YBCO films-100 kVA functional model", IEEE Trans. Appl. Supercond., Vol. 9, No. 2, pp. 656-659, June 1999.   DOI
2 T. Hara, T. Okuma, T. Yamamoto, D. Ito K. Tasaki, and K. Tsurunaga, "Development of a new 66.kV/1500A class superconducting fault current limiter for electric power system", IEEE Trans Power Delivery, Vol. 8, No. 1, pp. 182-192, Jan. 1993.   DOI
3 H. Kameda, and H. Taniguchi, "Setting Mothod of Specific Parameter of a Superconducting Fault Current Limiter Considering the Operation of Power System Protcetion", IEEE Trans. Appl. Superconduct., Vol. 9, No. 2, pp. June 1999.
4 S. H. Lim, "Operational Characteristics of Flux-Lock Type SFCL With Series Connection of Two Coils", IEEE Trans. Appl. Supercond., Vol. 17, No. 2, pp. 1895-1898, June 2007.   DOI
5 S. H. Lim, H. S. Choi, and B. S. Han, "Fault Current Limiting Characteristics due to Winding Direction between Coil 1 and Coil 2 in a flux-lock type SFCL", Phys. C, Vol. 416, pp. 34-42, Nov. 2004.   DOI
6 Y. Shirai, K. Fujikawa, T. Kitagawa, M. Shiotsu, H. Hatta, S. Muroya, and T. Nitta, "Study on recovery time of a superconducting fault current limiter with adjustable trigger current level", IEEE Trans. on Appl. Supercond., Vol. 11, No. 1, pp. 2086-2089, March 2001.   DOI
7 T. H. Han, H. S. Choi, S. H. Lim, and N. Y. Lee, "Recovery characteristics of flux-lock type superconducting fault current limiter", Physica C, Vol. 463-465, pp. 1209-1212, Oct. 2007.   DOI
8 H. Hatta, T. Nitta, S. Muroya, T. Oide, Y. Shirai, M. Taguchi, and Y. Miyato, "Study on recovery current of transformer type superconducting fault current limiter", IEEE Trans. on Appl. Supercond., Vol. 13, No. 2, pp. 2096-2099, June 2003.   DOI