Browse > Article
http://dx.doi.org/10.5207/JIEIE.2010.24.5.062

Characteristics of Transient Grounding Impedances of Counterpoises Relevant to the Injected Point of Impulse Currents  

Li, Feng (인하대학교 대학원 전기공학과)
Jung, Dong-Chul (인하대학교 대학원 전기공학과)
Kim, Jong-Ho (인하대학교 대학원 전기공학과)
Yoo, Jae-Duk (인하대학교 대학원 전기공학과)
Kim, Dong-Kyu (인하대학교 대학원 전기공학과)
Lee, Bok-Hee (인하대학교 IT공대 전기공학부)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.24, no.5, 2010 , pp. 62-69 More about this Journal
Abstract
This paper presents the dependances of transient grounding impedances of counterpoises on the soil structures and the injected point of impulse currents. The transient and conventional grounding impedances of the 25 and 50[m] counterpoises buried in the soil with different resistivity were measured and analyzed as a function of the rise time of impulse currents. As a result, the transient grounding impedances give an inductive behavior, and the trend of the conventional grounding impedances is similar to that of the transient grounding impedances. The ground resistance of counterpoises is irrespective to the injected of impulse current, but the transient and conventional grounding impedances in a short time range especially depend on the soil resistivity and position of the injected point of impulse currents.
Keywords
Impulse Current; Transient Grounding Impedances; Conventional Grounding Impedances; Soil Resistivity; Counterpoises;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 S. Visacro, “A didactic general approach of grounding behavior for lightning currents”, Proc. the 27th ICLP, Avignon, France, Vol. 1, pp. 508-513, 2004.
2 IEEE Std 81.2-1991, “IEEE Guide for Measurement of Impedance and Safety Characteristics of Large, Extended or Interconnected Grounding Systems”, IEEE Inc., pp..1731, 1991.
3 T. Takahashi, T. Kawase, “Calculation of Earth Resistance for a Deep-driven rod in Multi-layer Earth Structure”, IEEE Trans. on PD, Vol.6, No.2, pp.608-614, 1991.   DOI
4 B. H. Lee, D. C. Jeong, S. B. Lee and K. C. Chang, “Effective Impulse Impedances of Deeply Driven Grounding Electrodes”, KIEE Int. Trans on EA, Vol.4-C, No.5, pp.207-214, 2004.   과학기술학회마을
5 B. H. Lee, J. S. Park and S. C. Lee, “Experimental Investigations of Transient Impedances of Some Grounding Systems”, Proc. Korea Joint Syms. ED&HVE, pp.237-240, 1997.
6 이복희: 접지의 핵심 기초 기술, 도서출판 의제, pp.81-92, 1999.
7 KS C IEC 62305-1, 피뢰시스템-제1부: 일반원칙, pp.3-20, 2007.
8 N.Fujimoto, E. P. Dick, S. A. Boggs and G. L. Ford, “Transient Ground Potential Rise in Gsd-Insulated Substations-Experimental Studies”, IEEE Trans. on PAS., Vol.PAS-101, No.10, pp.3603-3609, 1982.   DOI
9 S. Karaki, et al, “Transient Impedance of GIS Grounding Grid”, IEEE Trans., Vol.PD-10, No.2, pp.723-738,1995.   DOI
10 이복희, 이수봉, 장근철, “형상이 다른 접지전극에 접속된 심매설 봉상접지전극의 임펄스접지임피던스 특성”, 조명전기설비학회논문지, Vol. 19, No.2, pp.63-69, 2005.   과학기술학회마을   DOI