Browse > Article
http://dx.doi.org/10.5207/JIEIE.2010.24.4.149

A Study on Selection of Cleaning Period and Pollution Analysis of Insulators in Tunnel  

Kim, Young-Seok (전기안전연구원 진단기술연구부)
Shong, Kil-Mok (전기안전연구원 진단기술연구부)
Choi, Myeong-Il (전기안전연구원 진단기술연구부)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.24, no.4, 2010 , pp. 149-155 More about this Journal
Abstract
This paper was carried out to estimate pollution levels of various insulators in tunnel and establish cleaning period in each tunnel section. We estimate pollution level that is attached to insulators in environmental pollution area, industrial area, salt damage area. These results that the pollution quantity and conductivity were increased by pollution accumulation period. However, the conductivity showed each other big difference in each tunnel. In particular, the conductivity showed big in environmental pollution(tunnel A) and salt damage(tunnel C) area, It is considered to prevent accident that manage establishing periodic state of cleaning plan. Also, the Grease that spread on the insulator surface in existing is considered that it can prevent accident for long-term by restrain use.
Keywords
Pollution; Insulator; Conductivity; Pollution qunatity; Tunnel;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 남정석, 김용기, 황종규, 한영재, 김현숙, “산업선 터널 및 공장 분진지역에서의 전철설비에 대한 안전대책연구, 한국철도기술연구원 보고서, 1996.
2 김영석, 송길목, 정진수, 정종욱, 김선구, “염수 및 분진에 의한 고분자 절연물의 표면누설전류 특성과 사고 위험성”, 한국조명전기설비학회, Vol. 21, No. 8, pp. 129-135, 2007.   과학기술학회마을   DOI
3 송길목, 김영석, 김선구, “현장 분진포집에 의한 도전율 측정과 전기설비 위험평가”, 한국조명전기설비학회 추계학술대회, 2007.
4 김찬영 외 5, “비용해성 산업용 분진이 배전용 자기제 현수애자의 전기적 특성에 미치는 영향”, 대한전기학회 Vol. 50C, No. 4, pp. 183-189, 2001.   과학기술학회마을
5 KSC IEC 60507(교류시스템에 사용되는 고압애자의 인공오염 시험), 기술표준원, 2005.
6 KSC 0223(환경시험방법(전기전자) 염수분무시험방법), 기술표준원, 2005.