A An Experimental Study for Load Capacity and Dip Characteristic in Overhead Transmission Lines  

Kim, Sung-Duck (한밭대학교 전기전자제어공학부)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.24, no.12, 2010 , pp. 177-183 More about this Journal
Abstract
Overhead transmission lines in domestic area have been built by several different design standards of dip and ground clearance. This paper describes an experimental study for evaluating load capacity and dip margin in overhead transmission lines. Such design standards for selection of overhead transmission conductors, dip and ground clearance, as well as electrical equipment technical standard are discussed. Based on daily load and weather data, several characteristics such as line utilization factor, load factor, conductor temperature and dip, etc. are analyzed, and compared with the specified levels of design standards. As a result, it is verified that DLR method can be a clue of the solving of the problem, for occurring in old transmission conductors which may be rarely operating below standards.
Keywords
Overhead Transmission Lines; Dip and Clearance; Load Factor; Dynamic Line Rating;
Citations & Related Records
연도 인용수 순위
  • Reference
1 국가표준기본계획, 산업자원부 공고 제2000 - 177, 2000. 11. 30.
2 김남호, 국제표준화 동향과 우리의 대책, 한국전기기술기준위원회, 2002.
3 가공송전선용 전선 선정기준 - 1210, 한계이도전선공사, 2003.
4 송전선로 지상고 설계기준 - 1020, 한계이도전선공사, 2003.
5 가공선 이도 설계기준 - 1211, 한계이도전선공사, 2003.
6 전기설비기술기준 및 판단기준. 2007년 1월, 산업자원부.
7 IEEE Standard for Calculating the Current-Temperature of Bare Overhead Conductors, IEEE Std 738-2006.
8 L. Ren, J. Xiuchen and S. Gehao, “DLR Research for dynamic increasing transmission capacity”, 2008 International Conference on Condition Monitoring and Diagnosis, Beijing China, 2008.   DOI