Abstract
This paper describes the safety assessment of power cable splices connecting different sized 6/10[kV] class power cables. To assess the safety, AC withstand voltage tests, partial discharge tests and impulse tests were carried out to the cable splice specimens and thermal rise due to overload and cross section of joint were examined as well. As a result, a breakdown due to the $4.5[U_0](27[kV_{ac}])$ application could not found for 5 minutes. Under $1.73[U_0](10.4[kV_{ac}])$ application, partial discharges of 4~8[pC] were detected. In impulse tests, all the specimens withstood to the standard waveforms of $75[kV_{peak}](1.2{\times}50[{\mu}s])$ without any breakdowns. In addition, the temperature on the splice rose by $3[^{\circ}C]$ when the 200[A] flew through the splice for 20minutes, however the thermal rise of $3[^{\circ}C]$ was considered due to the atmospheric temperature. After all the electrical tests, the cross section of the splice was visually examined. The conditions of the conductors of both $185[mm^2]$ and $240[mm^2]$ were good.
Keywords
Safety assessment; Power cable splices; AC withstand voltage tests; Partial discharge tests; Impulse tests; Thermal rise; Visual examination;
Citations & Related Records
연도 인용수 순위
  • Reference
1 한국전기안전공사, 전기재해통계분석, 지식경제부, 제18호, p.70, 2009.
2 김보경 외 3, 고압 및 특고압 전력케이블의 절연진단 및 유지보수 관리방법(1), 전력기술인, 2003. 11.
3 Dennis J. Wilkins, Part One - The Bathtub Curve, Infant Mortality and Burn-in, http://cxjr.21ic.org/user1/111/archives/2009/58265.html, 2009. 4.
4 정격 전압 1-30[kV] 압출 성형 절연 전력 케이블 및 그 부속품-제4부:정격 전압 6-30[kV] 케이블용 부속품에 대한 시험 요구, KSC IEC 60502-4 : 2006, 한국표준협회, p.7, 2006.