A Study on the Harmonic Characteristics of GHP Cooling/Heating Load in an Institutional Building  

Kim, Kyung-Chul (홍익대학교 전기공학과)
Oh, Kyung-Hoon (홍익대학교 대학원 전기공학과)
Lee, Kyu-Jin (홍익대학교 대학원 전기공학과)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.23, no.4, 2009 , pp. 29-38 More about this Journal
Abstract
The GHP(Gas Heat Pump) is an efficient cooling;11eating system in which a compressor is driven by a gas engine and is brodening its application to the facilities such as schools and office buildings. It is difficult to control the GHP system because of slow response, big time constant and time variant system. These nonlinear loads generate harmonic currents and create distortions on the sinusoidal voltage of the power system Harmonic field measurements have shown that the harmonic contents of a waveform varies with time. A cumulative probability approach is the most commonly used method to solve time varying harmonics. This paper provides an in depth analysis on harmonics field measurement of the GHP loads, harmonic assessment by me 61000-3-2, and harmonic simulation and harmonic filter application using EDSA program for the case study system.
Keywords
Gas Heat Pump; Harmonic Measurement; Harmonic Assessment; Harmonic Simulation; Harmonic Filter; IEC 61000-3-6;
Citations & Related Records
연도 인용수 순위
  • Reference
1 A. Toba, and et al., "PWM Rectifier with DC Reverseblocking Diode for High-Reliability Gemerating Apparatus and Its Application to Gas Heat Pump System", IEEE Power Electronic and Motion Control Conference, 2006
2 Y. Haseqawa, and et al., "Learning Predictive Control forGHP", IEEE Industrial Electronics Society, 2000
3 http:// www.overseas.sanyo.com/
4 IEC 61000-4-7, "General Guide on Harmonics andInter-harmonics Measurement and Instrumentation forPower Supply Systems", 2002
5 BMII-PX5, "Basic Measuring Instrument Power Xplorer",Dranez co., 2004
6 PQM Manual, "Power Quality Monitoring System", MicroPower Co., 2006
7 R. C. Dugan, and et al., "Electrical Power SystemsQuality", McGraw-Hill Co., 2003
8 IEEE Std P519A-1996, "Guide for Applying Harmonic Limits on Power Systems"
9 EDSA User's Guide, "Electrical Power System Harmonic Analysis Program", EDSA Micro Co., 2009
10 IEC 61000-3-6, "Assessment of Emissions Limits forDistorting Loads in LV Power Systems", 2005