Browse > Article
http://dx.doi.org/10.5207/JIEIE.2009.23.2.096

Relative Error Analysis for Measuring Value of Ground Resistance according to Position Variation of Potential Probe)  

Gil, Hyoung-Jun (한국전기안전공사 전기안전연구원)
Kim, Dong-Woo (한국전기안전공사 전기안전연구원)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.23, no.2, 2009 , pp. 96-102 More about this Journal
Abstract
In this paper, the effects of the position and the angle of the potential probes on the measurements of the ground resistance with the fall-of-potential method are described and the testing techniques to minimize the measuring errors are proposed. The fall-of-potential method is theoretically based on the potential and current measuring principle and the measuring error is primarily caused by the position and angle of auxiliary probes. In order to analyze the relative error for measuring value of ground resistance due to the position of the potential probe, ground resistance were measured in case that the distance of current probe was fixed at 50[m] and the distance of potential probe was located from l0[m] to 50[m]. Also, the potential probe was located at 30[$^{\circ}$], 45[$^{\circ}$], 60[$^{\circ}$], 90[$^{\circ}$] and 180[$^{\circ}$]. As a consequence, relative error decreased with increasing the distance of potential probe and decreasing the angle between current probe and potential probe. The results could be help to determine the position of potential probe when the ground resistance was measured at grounding system.
Keywords
Relative Error; Ground Resistance; Position Variation; Potential Probe;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 길형준, 최충석, 이복희, "개별 접지전극과 연접된 접지전극의 전위상승 분포 비교 연구", Vol.22, No.2, pp.57~62, 2008   과학기술학회마을   DOI   ScienceOn
2 길형준, 김동우, 김동욱, 이기연, 김향곤, "현장조사에 의한 접지시스템의 전기안전성 평가", 한국조명.전기설비학회 춘계학술대회, pp.361-364, 2008   과학기술학회마을
3 C. Wang, T. Takasima, T. Sakuta and Y. Tsubota, "Grounding Resistance Measurement Using Fall-of-PotentialMethod with Potential Probe Located in Opposite Direction to the Current Probe," IEEE Trans. Power Delivery, vol.13, no.4, pp.1128-1135, Oct. 1998   DOI   ScienceOn
4 R. Zeng, J. He and Z. Guan, "Novel Measurement System for Grounding Impedance of Substation," IEEE Trans. Power Delivery, vol.21, no.2, pp.719~725, Apr. 2006   DOI   ScienceOn
5 K. M. Michaels, "Earth Ground Resistance Testing for Low-Voltage Power Systems," IEEE Trans. Industry Applications, vol.31, no.1, pp.206-213, Jan./Feb. 1995   DOI   ScienceOn
6 V. Dimcev, B. Handjiski, P. Vrangalov and R. Sekerinska, "Impedance Measurement of Grounding Systems with Alternative Fall-of-Potential Method," IEEE Industry Applications Conference, vol.5, pp.3215-3219, 2000   DOI
7 TTAS.KO-04.0026/R1, "Technical Standard for the Measurements of Grounding Resistance," Telecommunications Tech. Ass., 2007
8 이복희, 이승칠, "접지의 핵심기초기술", 의제, pp.64-69, 1999
9 이복희, 엄주홍, "전위강하법에 의한 접지저항측정에 미 치는 전류보조전극의 영향", 한국조명.전기설비학회, Vol.14, No.6, pp.69~77, 2000   과학기술학회마을
10 IEEE Std 81-1983, "IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System", pp.19-23, 1983