Browse > Article
http://dx.doi.org/10.5207/JIEIE.2009.23.12.217

A Study on Characteristic for a Maximum Utilization Factor of Transformer with Regard to Load Characteristics in General Customers  

Kim, Se-Dong (두원공과대학 전기과)
Wang, Yong-Peel (한국전기산업연구원)
Hong, Hyun-Mun (통일부 교류협력국)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.23, no.12, 2009 , pp. 217-223 More about this Journal
Abstract
This paper shows a reasonable contract power conversion factor, that was made by the systematic and statistical way considering actual conditions, such as investigated contract power and peak power for the last 5 years of each customer for 461 general customers as to AMR. In this dissertation, it is necessary to analyze the key features and general trend from the investigated data. It made an analysis of the feature parameters, such as average, standard deviation, median, maximum, minimun and thus it was carried by the linear and nonlinear regression analysis. Therefore, this paper compared characteristics for a contract power conversion factor which is applied to estimate contract power with characteristics for a regression model for customers(office, store, hotel, hospital, wedding hall) which maximum utilization factor of transformer is more than 60[%].
Keywords
Contract Power Conversion Factor; Maximum Utilization Factor of Transformer; Transformer Capacity;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 전기공급약관, 한국전력공사, 2007
2 일본 전기공급약관, 동경전력(주), 2007
3 김세동, 왕용필, 일반용전력사용고객의 변압기최대이용률과 계약전력환산율 기준과의 비교특성 연구, 한국조명전기설비학회, Vol.22, No.5, pp.80-85, 2008