Browse > Article
http://dx.doi.org/10.5207/JIEIE.2009.23.10.128

The Comparison and Analysis about Earth Resistance for Measuring of Earth Resistance by Measurement Positions of Auxiliary Poles  

Han, Woon-Ki (한국전기안전공사 전기안전연구원 설비안전연구팀)
Jung, Jin-Soo (한국전기안전공사 전기안전연구원 설비안전연구팀)
Kim, Jae-Chul (숭실대학교 전기공학부)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.23, no.10, 2009 , pp. 128-133 More about this Journal
Abstract
This paper describes the comparison and analysis about measurement method of earthing resistance by positions of potential pole and current pole. In KOREA, a diagonal by 6.5 times of earthing electrode for measurement of earthing resistances but this method was almost impossible in the downtown area. For solving this problem, in this paper measuring of earthing resistance changing parameters. The parameter was a distances of earthing electrode, potential pole & current pole and the another parameter was an angles of potential pole & current pole. Analysis result, earthing resistance stability that conditions. Fist, distance from earthing electrode to current pole was over 50[m] and distance from earthing electrode to potential pole was over 30[m]. Second, angles of potential pole & current pole was over $45[^{\circ}]$.
Keywords
Earthing Electrode; Potential Pole; Current Pole; Electrode Distance; Pole Angle;
Citations & Related Records
연도 인용수 순위
  • Reference
1 IEEE Std 81.2-1991, "IEEE Guide for Measurement of Impedance and Safety Characteristics of Large, Extended or Interconnected Grounding Systems", IEEE Inc., pp.1731, 1991
2 산업자원부, '전기설비 기술기준 및 판단기준', 2006, 10
3 Ronald P. O' Riley, 2002, "Electrical Grounding", Delmar Thomson Learning, 202:p1-29
4 J. A. Guemes-Alonso et al, 2006, "A practical Approach for Determining the Ground resistance of Grounding Gride", IEEE transactions on Power Delivery, Vol.21 , No.3, pp.1261-1266, 2006   DOI   ScienceOn