Noise Elimination Algorithm for Detecting Partial Discharge of Generator Stator Winding Considering Relation of Periphery Signals  

Shin, Hee-Sang (숭실대학교 전기공학부)
Cho, Sung-Min (숭실대학교 전기공학부)
Kang, Chul (숭실대학교 전기공학부)
Kang, Dong-Sik (숭실대학교 전기공학부)
Cho, Kuk-Hee (숭실대학교 전기공학부)
Kim, Jae-Chul (숭실대학교 전기공학부)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.22, no.9, 2008 , pp. 17-24 More about this Journal
Abstract
Recently, the importance of supplying the reliable electric power is increasing. therefore, the importance of diagnosis of power equipments is increasing also. Breaking insulation of stator windings is major cause of faults in high voltage generators. On-line PD (Partial Discharge) detection using Capacitive Coupler at stator windings is used widely to diagnose high voltage generator. However, precise PD(Partial Discharge) detection is impossible if detected signals are mixed with PD and noise signal. In this paper, we analyze detected signals using Capacitive Coupler at 13[kV] hydroelectric generator stator winding and suggest not hardware method but noise elimination algorithm for detecting PD of generator stator winding considering relation of periphery signals.
Keywords
Partial Discharge; Noise Elimination; Stator Winding; Diagnosis;
Citations & Related Records
연도 인용수 순위
  • Reference
1 R.E.James and B.T.Phung, 'Development of computer- based measurements and their application to PD pattern analysis', IEEE Trans. Die. and Elect. Insul Vol. 7, No. 1, pp.57-63. 1997
2 동식 외, '고압 회전기 On-line 부분방전 측정용 Ceramic Coupler 특성', 대한전기학회 논문지, Vol. 51C No.5, pp. 205-212, 2002
3 K, Kimura, Y. Kaneda, K. Itoh, T. Kogi, K. Motooka, M. Takashima, 'On-line condition monitoring of winding insulation in turbine generators', proc. Of conference, CIGRE, 2000
4 박영훈, '부분방전 신호 중 노이즈 제거에 관한 연구', 포항공대 철강대학원 석사 학위논문, 2006
5 G. C. Stone and J.F. Kapler, 'Stator winding monitoring', IEEE IA Magazine, Vol. 4, No. 5, pp. 15-20, 1998
6 B.A. Lloyd, S.R. Campbell, G.C. Stone, 'Continuous on-line PD monitoring of generator stator windings', IEEE Trans EC, Dec. 1999, pp 1131-1137
7 W. McDermid, J.C. Bromley, 'Experience with directional couplers for partial discharge measurements on rotating machines in operation', IEEE Trans. EC, June 1999, pp175-184