An Elimination Method Of the Circulating Current Flowing into Coaxial-Neutral Lines in 22.9[kV] CNCV Underground Cable Systems  

Jeon, Myung-Su (서울산업대)
Song, Joong-Ho (서울산업대학교 전기공학과)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.22, no.2, 2008 , pp. 107-113 More about this Journal
Abstract
In 22.9[kV]-y distribution systems, underground cables are provided with multiple-point ground in which each coaxial-neutral line of the distribution cable lines(A, B, C phases) is 3-wire common grounded. In the underground cable distribution systems, circulating current flows in the coaxial-neutral lines and its magnitude amounts to about $40{\sim}50[%]$ load currents, even though loads are balanced. Power loss due to the circulating current consequently reaches to about 76[%] total losses occurred in all conductor lines. This power loss provokes additional temperature rise of the underground cable lines and finally results in 20[%] reduction of the current capacity of the cables. This paper presents a new ground method to overcome such a problem. The proposed method eliminates the circulating current flowing in the coaxial-neutral line effectively. Measurement results confirmed from the practical site-test show validity and effectiveness of this research.
Keywords
Corculating current in co-axial neutral lines of distribution cables; Multiple-point ground; 22.9[kV] CNCV distribution system;
Citations & Related Records
연도 인용수 순위
  • Reference
1 '지중편설계기준 1650', 한국전력공사, 2004
2 '배전규정', 대한전기협회 배전규정전문위원회, 1997
3 '배전지중설계기준 5900부록', 한국전력공사, 2003
4 한전표준구매시방서, '22.9[kV] 동심중성선 전력케이블', ES-126-650-664, 한국전력공사, 2001
5 김복현, '22.9[kV] CV/CN케이블의 중성선 전류가 허용전류에 미치는 영향', 석사 논문, 연세대학교, 1987
6 'IEEE guide for the application of sheath-bonding methods for single-conductor cables and the calculation of induced voltages and currents in cable sheaths', ANSI/IEEE Standard 575, 1988
7 경영정보처. '전력통계15, 배전설비추이', 한국전력공사, 2005