The Accident Hazards and Properties of the Surface Leakage Current on the Polymer Insulation caused by Salt-water and Dust  

Kim, Young-Seok (전기안전연구원 설비안전연구그룹)
Shong, Kil-Mok (전기안전연구원 설비안전연구그룹)
Jung, Jin-Su (전기안전연구원 설비안전연구그룹)
Jung, Jong-Wook (전기안전연구원 설비안전연구그룹)
Kim, Sun-Gu (전기안전연구원 설비안전연구그룹)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.21, no.8, 2007 , pp. 129-135 More about this Journal
Abstract
It is necessary to study on the prevention and the management of electrical facilities because the electrical fault took place at the dust occurrence area due to environmental pollution. In particular, the dust accumulates easily on insulation material which is exposed an external long time. Therefore, we measured surface leakage current and surface variation of insulation material due to the dust and salt-water. From the results, the surface of bakelite is bad effect for salt-water than other material. The surface leakage current increases by repeated salt-water pollution and the surface of material is carbonized with arc occurrence. Also, it is need to variation of surface coating and shape of material to repress a leakage current on electrical material.
Keywords
Dust; Pollution; Electrical Fault; Leakage Current; Prevention;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 IEC 60112 Ed. 4.0 b, 'Method for the determination of the proof and the comparative tracking indices of solid insulating materials', 2003
2 한국전기연구원, '초고압 LSR 개발 및 절연물의 복합 열화 진단기술 연구, 최종보고서, pp.55-58, 1999
3 S.Kumagai and N. Yoshimura, 'Impact of Thermal Aging and Water Absorption on the Surface Electrical and Chemical Properties of Cycloaliphatic Epoxy Resin', IEEE Trans. DEI Vol. 7, No. 3, pp.424-431, 2000   DOI   ScienceOn
4 박재준, 최인혁, 이동일, ' 여러 환경조건에 대한 고분자 애자의누설전류 특성 변화', Journal of the Korea Institute of Electrical and Electronic Material Engineers, Vol. 19, No. 2, pp.169-175, 2006   DOI   ScienceOn
5 김찬영, 송일근, 김주용, 한재홍, 김동명, 이병성, '비용 해성 산업용 분진이 배전용 자지제 현수애자의 전기적 특성에 미치는 영향', Trans. KIEE. Vol. 50C, No. 4, pp. 182-189, 2001
6 한국전기안전공사, '2005년도 통계자료', pp.4-30, 2005
7 KS C IEC 60068-2-68, '환경시험-제2부:시험-시험 L:분진 및 모래', 기술표준원, 2003 제정
8 송길목 외 2, '누전차단기 외함 전원측 단자사이의 트래킹에 의한 탄화특성 분석', 한국화재소방학회 논문지, Vol. 17, No. 4, pp.13-19, 2003