Browse > Article
http://dx.doi.org/10.5207/JIEIE.2006.20.5.072

Comparison of Measured Data and Theoretical Results for Potential Rise of Structure Using Electrolytic Tank Model  

Gil, Hyoung-Jun (전기안전연구원)
Kim, Dong-Woo (전기안전연구원 재해예방연구그룹)
Choi, Chung-Seog (전기안전연구원 재해예방연구그룹)
Lee, Bok-Hee (인하대 공대 전자전기컴퓨터공학부)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.20, no.5, 2006 , pp. 72-77 More about this Journal
Abstract
This paper presents a comparison of experimental value by electrolytic tank experimental apparatus and calculated value by CDEGS program for potential rise of structure. When a test current flowed through structure models, potential rise was measured and analyzed for types of structure using the electrolytic tank experimental apparatus in real time, and was computed by means of CDEGS program. The structure models were designed and fabricated with four types on a scale of one-one hundred sixty. When the experimental data were compared with the theoretical values, the similar profile was shown. Therefore, the confidence of measurement was obtained. Potential rise was the lowest value at electric cage type(structure model B). The distributions of potential rise are dependent on the resistivity and absorption percentage in concrete attached to structure.
Keywords
Electrolytic tank experimental apparatus; Potential rise; Structure model;
Citations & Related Records
연도 인용수 순위
  • Reference
1 F. Dawalibi, D. Mukedkar, 'Optimum Design of Substation Grounding in a Earth Structure : Part II-Comoarison between Theoretical and Experimental results', IEEE Trans. PAS., Vol. PAS-94, No.2, pp.262-266, 1975
2 Chung-Seog Choi, Hyang-Kon Kim, Hyoung-Jun Gil, Woon-Ki Han, Ki-Yeon Lee, 'The Potential Gradient of Ground Surface according to Shapes of Mesh Grid Grounding Electrode Using Reduced Scale Model', IEEJ Trans. PE. Vol. 125, No. 12, pp.1170-1176, 2005   DOI   ScienceOn
3 길형준, 최충석, 이복희, '반구형 접지모의시스템을 이용한 접지전극의 형상에 따른 내지전위상승의 분석', 대한전기학회, Vol. 54C, No. 7, pp.319-325, 2005
4 IEC Pub. 1200-413, 'Electrical Installations Guide. Part413 ; Protection against Indirect Contact Automatic Disconnection of Supply'. pp.9-19, 75-84. 1996
5 IEC Pub. 364-413, 'Electrical Installations of Building, Part4 ; Protection for Safety, Chapter41 ; Protection against Electric Shock'. pp.25-37. 1999
6 F. Dawalibi, D. Mukedkar, 'Optimum Design of Substation Grounding in a Earth Structure : Part I-Analytical Study', IEEE Trans. PAS., Vol. PAS-94, No. 2, pp.252-261, 1975
7 R. Cadecott, D.G. Kasten, 'Scale Model Studies of Station Grounding Grids', IEEE Trans. PAS., Vol. PAS-102, No.3, pp.558-566, 1975
8 이복희, '접지의 핵심기초기술', 의제, pp.179-190, 2000
9 Ronald P. O'Riley, 'Electrical grounding', Delmar Thomson Leaming, pp.1-29, 2002
10 이복희, 이승칠, 엄주홍, 김효진, '보조접지전극의 시설에 의한 대지표면전위경도의 저감', 한국조명 . 전기설비학회 논문지, Vol. 16, No. 2, pp.121-129, 2002