Abstract
This paper presents the transient impedance behaviors according to the length of down conductors of grounding systems to lightning impulse currents. The potential rise and effective impulse ground impedance of the deeply-driven ground rod and grounding grid subjected to the impulse currents were measured and analyzed as a function of the rise time of impulse currents and lengths of down conductor. The transient ground impedances strongly depend on the configuration and size of grounding electrodes, the waveform of impulse currents and the length of down conductors, and the installation methods reducing the inductance of down conductors are an important factor to decrease the transient ground impedances.
Keywords
Down conductor; Impulse ground impedance; Impulse current; Ground rod; Grounding grid;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Bok-Hee Lee,Dong-Cheol Jeong, Su-Bong Lee and Keun-Chul Chang, 'Effective Impulse Impedances of Deeply Driven Grounding Electrodes', KIEE International Trans on EA, vol. 4-C, no. 5, pp. 207214, 2004
2 S. Karaki, et al, 'Transient Impedance of GIS Grounding Grid', IEEE Trans., Vol.PD-10, No.2, pp.723-738, 1995
3 IEEE Std 81.2-1991, 'IEEE guide for Measurement of Impedance and Safety Characteristics of Large, Extended or Inter connected Grounding System', IEEE Inc., pp. 17-31, Dec. 1991
4 B. H. Lee, J. S. Park and S. C. Lee, 'Experimental Investigations of Transient Impedances of Some Grounding Systems', 1997 Japan-Korea Joint Syms. ED & HVE, pp.237-240, 1997
5 B. R. Gupta and B. Thapar, 'Impulse Impedance of Grounding Grids', IEEE Trans. Vol.PAS-99, No.6, pp.214-218, 1980
6 Z. Stojkovic, M.S. Savic, J.M. Nahman, D. Salamon and B. Bukorovic, 'Sensitivity Analysis of Experimentally Determined Grounding Grid Impulse Characteristics', IEEE Trans., Vol. PD-13, No. 4, pp.1136-1141, 1998
7 IEEE Std 1100-1999, IEEE Recimmended Practice for Powering and Grounding Electronic Equipment, IEEE Inc., pp.38-44, pp.128-129, 1999
8 T. Takahashi, 'A Part of Grounding for Lightning Protection Technique', J. IEE of Japan, Vol.9, pp.671- 676, 1989
9 C. W. Barnett, B. L. Laird, J. L. Blackburn, W. C. Kotheimer, J. R. Linders, D. R. Volxka, J. A. Zulaski, and J. W. Walton, 'Summery of the Gride for the Grounding of Instrument Transformer Secondary Circuits and Case', IEEE Trans. on PD, Vol.3, No. 4, pp.1459-1465, 1988