The Heating Characteristics of Electric Bare Wire Melted by AC Current  

Shong, Kil-Mok (전기안전연구원 전기재해연구그룹)
Choi, Chung-Seog (전기안전연구원 전기재해연구그룹)
Kim, Hyong-Kon (전기안전연구원 전기재해연구그룹)
Kim, Young-Seok (전기안전연구원 전기재해연구그룹)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.20, no.1, 2006 , pp. 77-84 More about this Journal
Abstract
For a fire cause judgement this paper describes the heating characteristics of electric bare wire melted by AC current. The cower wires prepared for the experiment were 1.2[mm], 1.6[mm], and 2.0[mm] in diameter. Through the cross section analysis(CSA), it was confirmed that the dendrite structure grew at the angle of about 40[$^{\circ}$] or 60[$^{\circ}$] when the fusing current was applied to the wires. The larger the fusing current is, the more decreased the growth angle of the dendrite structure is. It was confirmed that the dendrite structure was arranged like the columnar structure.
Keywords
fire cause judgement; heating characteristics; fusing current; dendrite structure; columnar structure;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Chung-Seog Choi, Kil-Mok Shong, Hyang-Kon Kim, Dong- Ook Kim, Dong-Woo Kim, 'The Analysis of Dendrite Structure of Electric Wire Melted by Fusing Current', 2003J-K Joint Symp. on ED&HVE, pp.145-148, 2003
2 John D. DeHaan, 'Kirk's Fire Investigation', 5th edition, Prentice Hall, pp.305, 2002
3 Kil-Mok Shong, Hyang-Kon Kim, Chung-Seog Choi and Hee-Ro Kwak, 'A Study on the Electrical Fire Analysis of PVC Insulateds Flexible Cord by Over-Current', KIEE 2003spring conference, pp.131-133, 2003
4 Atila Metrol Member, 'Estimation of Aluminium and Gold Bond Wire Fusing Current and Fusing Time', IEEE Trans. on CP & MT, VOL. 18, NO. 1, pp.210-214, 1995
5 김정근 외 2, '금속현미경 조직학', 도서출판 골드 초판, pp.14-183, 1999
6 William D. Callister, Jr., 'Materials Science and Engineering an Introduction', Wiley 6th edition, pp.594-636, 2003
7 Eugene Loh, 'Physical Analysis of Data on Fused -Open Bond Wires', IEEE Trans. on CH & MT, VOL. CHMT-6, NO. 2, 1983
8 Babrauskas, V., 'Fires due to Electric Arcing: Can 'Cause' Beads Be Distinguished from 'Victim' Beads by Physical or Chemical Testing?', Fire and Materials, pp.189-201, 2003
9 W.H. Preece, 'On the heating effects of electric currents' , Proc.Royal Soc., vol. 36, pp.464-471, 1884   DOI
10 Sheera Knechi, Bill Gonzalez, Kimberley Sieber, 'Fusing Current of Short Aluminum Bond Wire', 1996 InterSociety Conf. on TP, pp.329-333, 1996