Browse > Article
http://dx.doi.org/10.5207/JIEIE.2006.20.1.034

The Characteristics Analysis of New Dc 48[V] Telecommunication Power System using Forward Type three Phase Rectifier  

Suh, Ki-Young (경남대학교 전자전기공학부)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.20, no.1, 2006 , pp. 34-40 More about this Journal
Abstract
This paper proposed power system for new DC 49[V] telecommunication using forward three-phase PWM rectifier power factor and efficiency for improvement of ripple voltage. Proposed power system for DC 48[V] telecommunication that consists of power conversion devices including switch, inductor and condenser were made between each line, in power inverter device of each switch control turn-on in period of continuity time control to get power factor '1' of sine wave current and on-off of switch lessens peak current that was happened and got conversion efficiency 92.1[%] composing in PWM rectifier of forward form instead of general PWM rectifier. Also, harmonic input regulation value(IEC61000-3-2 Class-As) satisfy input current and reduce ripple factor of output voltage in state that distortion of three-phase supply is overlapped each other.
Keywords
Telecommunication; IEC61000-3-2; High-Frequency isolated;
Citations & Related Records
연도 인용수 순위
  • Reference
1 IEC61000-3-2(1995-03), 1997.12
2 鈴木, 飯野, 木暮, 高田, 'ソフトスイッチング高力率整流器', Origin Technical Journal, No.60, pp.5-12, 1997
3 J.Minbock, 'Design and Experimental Investigation of a Single-Switch Three-Phase Flyback-Derived Power Factor Corrector,' proceedings of IEEE INTELEC, Vol.25, No.3, pp.471-478, 2000
4 長井眞一郞,森田浩一,'高効率 3相ソフトスイッチング力 率改善回路',平成11年電氣學會産業應用部門全國大會講演論文集, Vol.3, 280, pp.207-212, 1999
5 L. Malesani, V. Toigo, 'A Synchronized Resonant DC Link Converter for Soft-Switched PWM', IEEE Transantion on Industry Applications, Vol.29, No.5, pp.940-948, 1993   DOI   ScienceOn
6 佐藤伸二,末廣豊, '齟i方式三相PWM整流器による正弦波 入力電流制御'C電子情報通信學會總合大會講演 論集通信[2], SB-8-1, pp.717-718, 2001
7 Yutaka Suehiro, Masayoshi Yamamoto, Mutsuo Nakaoka, High Power Factor 3 Phase PWM Rectifier, IEEE intelec02, 19-2, pp.303-308, 2002
8 末廣 豊, 佐藤 伸二, '整流器ユニットRSD48-100TPの開發', サンケン技報 vol.34,No.1, pp.15-18, 2002
9 豊田直樹,高田忠明,'力率改善機能付大容量スイッチング整流器', サンケン技報, Vol.29, No.1, pp.71-75, 1997