Browse > Article
http://dx.doi.org/10.5207/JIEIE.2005.19.3.027

A Study on DC Changing Algorithm of the Line-Interactive UPS with Dual Converter Structure  

Lee, Woo-Cheol (한경대학교 전기공학과)
Yoo, Dong-Sang (한경대학교 전기공학과)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.19, no.3, 2005 , pp. 27-34 More about this Journal
Abstract
This paper presents a three phase Line-Interactive uninterruptible power supply(UPS) system with dual converter structure. The three phase UPS system consists of two active power compensator topologies. One is a series active compensator, which works as a voltage source in phase with the source voltage to have the sinusoidal source current and high power factor under the deviation and distortion of the source voltage. The other is a parallel active compensator, which works as a conventional sinusoidal voltage source in phase with the source voltage, providing to the load a regulated and sinusoidal voltage with low total harmonic distortion(THD). This paper presents in the series and parallel active compensator charging method depending on the amplitude of the source voltage. The conventional Line-Interactive UPS system is responsible for the DC charging and output voltage regulation at the same time, but UPS system with dual converter structure, a series active compensator can also charge the DC link. Therefore the charging algorithm using the series and parallel compensator needs to be researched. Therefore, by making the DC link voltage stable it can contribute the stability of series and parallel compensator. The simulation and experimental result are depicted in this paper to show the effect of the proposed algorithm.
Keywords
Line-Interactive UPS; dual converter structure; DC charging;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Kamran, F. and Habetler, T., 'A Novel On-Line UPS with Universal Filtering Capabilities.' IEEE/PESC, pp. 500-506, 1995
2 Soren Rathmann, Henry A. Warner, 'New generation ups technology, The delta conversion principle.' IAS 96, Conference Record of the 1996 IEEE, vol.4, pp.2389-2395, 1996
3 Sergio augusto Oliveira da Silva, Pedro F. Donoso Garcia, 'A comparative analysis of control algorithms for three phase line interactive ups systems with series parallel active power line conditioning using SRF method.' PESC00. IEEE vol.2, pp.1023-1028, 2000
4 Silva, S.A.O., Donoso-Garcia, p.; Cortizo, P.C.; 'A Three-Phase Series-Parallel Compensated Line-Interactive UPS System with Sinusoidal Input Current and Sinusoidal Output Voltage.' IAS, Conference Record of the 1999 IEEE, vol.4, pp.826-832, 1999
5 W. J. Ho, et al, 'A Line-interactive UPS Structure with Built-in Vector-Controlled Charger and PFC', in Power Electronics and Drive Systems, vol. 1, pp. 127-132, 1997
6 Dougls C. Folts, 'The response of Advanced Single-Conversion UPS to Power Disturbances.' Seventh International Power Quality Conference, October 1993 Proceedings. pp. 93-105
7 Taeck-Kie Lee; Woo Cheol Lee; Hoon Jang; Dong-Seok Hyun, 'A Study on the Line-Interactive UPS using the Series Voltage Compensator' IEEE, IECON Conference Proceedings, 2002. vol. 1, pp. 733-738, 2002
8 Oliveria da Silva, S.A.; Donoso-Garcia, p.; Cortizo, D.C.; 'A Three-Phase Line-Interactive UPS System Implementation with Series-Parallel Active Power-Line Conditioning Capablilites.' IAS, Conference Record of the 2001 IEEE, vol.4, pp.2389-2396, 2000
9 Seong-Jeub Jeon; Gyu-Hyeong Cho, 'A series-parallel compensated uninterruptible power supply with sinusoidal input current and sinusoidal output voltage' PESC '97 Record, IEEE vol.1, pp.297-303, 1997