Browse > Article
http://dx.doi.org/10.5207/JIEIE.2004.18.5.183

Research of Stresses Distribution and Loading Weight on Concrete Electric Pole Considering Field Condition  

Kim, Dong-Myung (전력연구원 배전연구센터)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.18, no.5, 2004 , pp. 183-188 More about this Journal
Abstract
A method of double-pole construction is developing to strengthen the mechanical intensity of the electric poles. Therefore the mechanical properties of the double-pole were researched in this paper. First, considering field special quality electric poles were established. In the next tensile force was applied and stress distribution and fatigue load were examined. When a base of the pole is concrete, mechanical intensity of the double-pole increased about 1.7 times compared a single pole. In the case of general soil base, the concrete base should be needed to expect the reinforcement effect of the double-pole.
Keywords
Concrete pole; tensile force; mechanical intensity; double-pole;
Citations & Related Records
연도 인용수 순위
  • Reference
1 한국전력공사, '배전실무교육교재', p.4, 2004
2 ES 102-128~617
3 KS F 2454
4 KS F 4304
5 Annual Book of ASTM Standards, VoI.01.04
6 Annual Book of ASTM Standards, VoI.04.08
7 Reece, L. C., 'Design and Evaluation of Load Tests on Deep Foundations', ASTM STP 670, Am. Soc. Testing Mats., 1979
8 臺灣電力, '設計基准', 第 2章 架空電線路 第 205節 支持物(雙抱電桿強度計算)