Abstract
A size of low-voltage conductor cables is determined by the voltage drop of a system the cable impedance and the cable ampacity based on temperature correction factor in accordance with the condition of cable installation. Therefore, the proper temperation correction factor according to the condition of cable installation should be applied to determining the cable ampacity and also the skin effect and proximity effect, along with the kind and size of conductor and the condition of cable installation, should be properly considered to analyze the proper value of resistance and the reactance of the conductors. This paper addresses the systematic design flow for determining the size of low voltage level con여ctor cables in calculating the voltage drop of a power system and proposes a new improved the calculating formula what error should be minimized in comparison with the general formula and which can be applied in design work for determining the size of conductor cables.
Keywords
Low-voltage conductor cables; Improved the calculating formula; Size conductor cables;
Citations & Related Records
연도 인용수 순위
  • Reference
1 IEC 949-1988[Calculation of Thermally Permissible Short-Circuit Currents, taking into account Non-Adiabatic Heating Effects].
2 “전기 설비 기술계산 핸드북”, 기다리, pp. 115-170.
3 IEEE 835-1994[IEEE Standard Power Cable Ampacity Tables].
4 최홍규외, “전력 사용시설물 설비 및 설계”, 성안당, pp. 245-398, 1999.
5 IEEE S-135-1-1962(ICEA P-46-426)[Power Cable Ampacities Volume 1-Copper Conductors].
6 KS C 4202-1977 [일반용 저압 3상 유도 전동기].
7 Microsoft Excel2000.
8 新版.電力 ケ-ブル 技術 ハンドブック, 電氣書院, 1989.
9 KS C 3611-1933 [600V 폴리 에틸렌 케이블].
10 NEC HANDBOOK-1999 Article 310[Conductors for General Wiring].
11 JCS 168E - 1995 [전력 케이블 허용전류-1].
12 NEMA WC52-1986(ICEA P-54-440)[Ampacities of Cables in open-top Cable Trays].