Browse > Article
http://dx.doi.org/10.5207/JIEIE.2002.16.3.047

Analysis on Thermal Transfer Characteristics of 50 kVA Mold-Transformer  

이현진 (인하대학교 전기공학과)
정중일 (인하대학교 전기공학과)
허창수 (인하대학교 전기공학과)
조한구 (인하대학교 전기공학과)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.16, no.3, 2002 , pp. 47-54 More about this Journal
Abstract
This paper presented the charcteristic of the thermal transfer in a 50[kVA] cast-resin dry type transformer. The conductivity of the primary winding composed were a Plenty of epoxy-resin ard a little of Cu was determined by that rating. Otherwise the conductivity of the secondary winding composed of a plenty of Cu and a little of epoxy-resin was determined by comparing the data of analysis using FEM method with those of temperature tests of the prototype cast-resin transformer. Based on the reults of the physical characteristics and the simulation by commercial using FEM method we established the prototype Model for this test. According to that Model, an analysis on variation of the temperature was discussed as a function of ambient temperature and velocities in the 50[kVA] cast-resin dry type transformer.
Keywords
Transformer; FEM; Thermal simulation; Epoxy resin; Hole;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Takashi Hasegawa, “Application Technology of Molded Products in the Field”, Takaoka Review, 1996.
2 임달호, “전기계의 유한요소법”, 동명사, pp. 1-5, 1992.
3 T. Chao, “Solid cast transformers”, IEEEIAS Pulp Paper Conf, pp. 140-147, 1991.
4 H.G.Cho, et.al, “The Temperature Distribution and Thermal Stress Analysis of Pole Mold transformer”, B.KIEEME, No. 4, pp. 297-301, 2001.   과학기술학회마을
5 Linden W. Pierce, “Specifiying and Loading Cast-Resin Transformers”, IEEE Trans. Industry Applications. Vol. 29, no. 3, pp. 590-599, May/June, 1993.   DOI   ScienceOn
6 오무송외 1, “전기기기설계”, 형설출판사, 1996.
7 W.E Featheringill, “Power transformer Loading”. IEEE Trans. Industry Applications, Vol. 1A-19, no. 1, pp. 21-27, Jan./Feb. 1983.
8 “고체 물리학 실험”, 경희대학교 물리학과.
9 Linden W. Pierce, “Predicting Hottest Spot Temperatures in Ventilated Dry Type Transformer Windings”, IEEE Trans. Power Delv., Vol.9, No.2, April 1994.
10 A. Rernandes-Costa et al, “Prevision of The Thermal Behavior of Dry Type Cast Resin Transformers”, Electric Machines and Power Systems, 20:261-272, 1992.   DOI   ScienceOn
11 “A Study on the Electrical Material”, KERI, pp. 21-24, 1987.
12 Linden W. Pierce, “An Investigation of the The Temperature Distribution in Cast Resin Transformer Windings”, IEEE Trans. Power Delv., Vol.7, No.2, April 1992.
13 IEC 726, “Dry Type Power Transformers”, 1982.
14 천희영외 1, “전기기계”, 청문각, 1995.