Browse > Article
http://dx.doi.org/10.5207/JIEIE.2002.16.2.059

A Study on the Electric Field Analyses and Improvement of Insulation Characteristics on the Ribbed Spaced for GIS  

류성식 (현대중공업 기전연구소 연구원)
최영찬 (현대중공업 기전연구소 책임연구원)
곽희로 (숭실대 공대 전기공학과)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.16, no.2, 2002 , pp. 59-64 More about this Journal
Abstract
This paper analyzed the effect of ribs on the breakdown characteristics when a metallic particle attaches on the various spot of GIS spacer, using electric field analysis. Also, it was compared with the experimental result of breakdown voltage characteristics for the spacer with a metallic particle on its various spot and with the shape, the length, and the thickness of the ribs varying. The results of electric field analysis show that the electric field concentration of the rib is more weakened than other parts and therefore it restrains the proceeding of streamer, which occurs at the breakdown. And it is verified through experiments that the breakdown voltage of the spacer with rib is higher than that of the spacer without rib. The breakdown characteristics depend on the shape, the length, and the thickness of the rib as well. Also, it is confirmed by the electric field analysis and the experimental results that the electric breakdown characteristics could be improved by rounding the rib edge.
Keywords
GIS; rib; sparer; electric field analysis; breakdown voltage; sreamer;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Fumihiro Endo et al, "Enhancement of Insulation Reliability of GIS", Japan-Korea Symposium on ED and HVE, pp. 5-10, 1997.
2 류성식, 최영찬, 곽희로, “GIS 립 스페이서에 의한 파괴 전압 특성 개선”, 조명․전기설비학회 논문지, Vol. 15, No. 5, pp. 28-33, 2001.
3 류성식, 곽희로 외, “개선된 GIS 스페이서의 전계해석 및 파괴전압 특성”, 대한전기학회 하계학술대회 논문집, C권, pp. 1921-1923, 2000.
4 김익모 외, “765kV GIS 기초설계기술 개발”, 현대중공업 연구보고서, HEMRI-01-02-D007, pp. 152-155, 2001.
5 권동진 외, "변전설비 진단기술 개발 연구(최종보고서)", 전력연구원, pp. 69-108, 1998.
6 윤덕량 외, "GIS 무정전 점검기법 연구(최종보고서)," 한국전기안전공사, pp. 1-131, 1996.
7 류성식, 곽희로 외, “GIS 립-스페이서의 형상에 대한 전계해석 및 파괴전압특성”, 대한전기학회 방전 및 고전압연구회 춘계학술발표대회 논문집, pp. 107-109, 2000.
8 Tokio Yamagiwa et al, "Particle-initiated Breakdown Characteristics on a Ribbed Spacer Surface for $SF_6$ Gas Insulated Switchgear", IEEE Transactions on Power Delivery, Vol. 3, No. 3, pp. 954-960, 1988.   과학기술학회마을   DOI   ScienceOn