Browse > Article

Dynamic Characteristics Analysis of Closing Resistors of Gas Insulated Switchgear  

Cho Hae-Yong (충북대학교 기계공학부)
Lee Sung-Ho (LS산전(주))
Lim Sung-Sam (LS산전(주))
Lee Ki-Joung (LS산전(주))
Kim Min-Woo (충북대학교 정밀기계공학과)
Publication Information
Abstract
GIS(Gas Insulated Switchgear) is used in electric power system, to insure non conductivity, breaking capacity and operating reliability. The commercial dynamic analysis code COSMOS MOTION and 3-D modeling program SOLID WORKS were used to simulate dynamic analysis of the closing resistors of the GIS in this paper. To reduce chatter vibration of closing resistors, the motion of moving and fixed parts of closing resistors were simulated by varying the spring constant, the damping coefficient and the mass of moving and fixed parts. The simulated results were compared with experimental results. As a result, chatter vibration of closing resistors of the GIS could be reduced by using the results. These data can be used to determine the spring constant, the damping coefficient and mass of a moving part to reduce chatter vibration when the next model is developed.
Keywords
Gas Insulated Switchgear; Dynamic Analysis; Chatter Vibration; Closing resistors;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Legate, A. C., Brunke, J. H., Ray, J. J. and Yasuda, E. J., 'Elimination of closing resister on EHV circuit breakers,' IEEE Transactions on Power Delivery, Vol. 3, Issue 1, pp. 223-231, 1998   DOI   ScienceOn
2 Kim, J. B., Chung, Y. H. and Song, W. P., 'The Study on Application of Circuit Breaker Without Closing Resister in Short Transmission Line,' Trans. of KIEE, Vol. 53A, No. 1, pp. 31-37, 2004
3 Kim, Y. G., Yoon, S. J., Moon, K. L. and Seo, J. M., 'Impact Analysis of Circuit Breaker by an Elastic-Plastic FEM,' Proceedings of the KIEE Autumn Annual Meeting, pp. 645-648, 1999
4 Ochiai, I., Kohyama, H., Ito, H., Hidaka, M., Sugiyama, T., Yamamoto, H. and Matuszak, D., 'Development of 550kV 63kA one-breaker gas circuit breaker,' Transmission and Distribution Conference and Exhibition 2002 : Asia Pacific IEEE/PES, Vol. 1, pp. 93-98, 2002   DOI
5 Ahn, K. Y. and Jeong, K. Y., 'Optimization of the Spring Design Parameters of a Circuit Breaker for Satisfying Specified Dynamic Characteristics,' Journal of the KSPE, Vol. 21, No. 3, pp. 132-138, 2004   과학기술학회마을
6 Lee, Y. H., Lee, H. D., Park. J. N., Shin, Y. S., Park, J. S. and Seo, J. M., 'Characteristic as a Resonance Frequency of $SF_6$ Gas,' Proceedings of the KIEE Summer Annual Meeting, pp. 112-114, 2003
7 Lee, S. H., Min, K. S., Park, S. W., Kang, S. M., Lee, J. T., Park, K. Y., Shin, P. S. and Ko, D. S., 'Development of Gas Circuit Breaker for 1 Break of 362kV 63kA 8000A,' The Second National Symposium on Electric Power Apparatus, Materials and Their Application, pp. 120-122, 1998
8 Chen, Fu-chen, 'Dynamic response of spring-type operating mechanism for 69kV $SF_6$ gas insulated circuit breaker,' Mechanism and Machine Theory, Vol. 38, pp. 119-134, 2003   DOI   ScienceOn