Comparison of SE Evaluation Methods for HEMP Shelters  

Chung, Yeon-Choon (Department of Electronics, Seokyeong University)
Lee, Jongkyung (E&R Tech.)
Kwun, Suk-Tai (E&R Tech.)
Publication Information
Abstract
Two test standards to be applied for evaluating shielding effectiveness of HEMP protection facilities, MIL-STD-188-125-1 and IEEE std. 299, provide different test results in spite of the same facility. In particular, at the frequency range of 10 kHz~20 MHz, it is confirmed that the test results by the IEEE Std. 299 are about 20~30 dB lower than the evaluated results by MIL-STD-188-125-1. These results are due to the different measurement conditions specified in the two test standards. Therefore, IEEE Std. 299 can be applied for the shortening of test distance, but the required SE performance based on MIL-STD-188-125-1 must be modified.
Keywords
HEMP Shelter; Shielding Effectiveness; MIL-STD-188-125-1/2; IEEE std 299;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 IEEE-STD-299, "IEEE standard method for measuring the effectiveness of electromagnetic shielding enclosures", Feb. 2007.
2 George H. Baker, Clinton R. Gordon, "Progress in the development of HEMP protection standards for C3I facilities", Proc. of IEEE EMC Symp., pp. 52-53, Austin TX. 17-21 Aug. 1989.
3 Manjung Seo, Seongwon Chi, Youngjin Kim, Woochul Park, Hojae Kang, and Changsu Huh, "Electromagnetic wave shielding effectiveness measurement method of EMP protection facility", The Journal of Korean Institute of Electromagnetic Engineering and Science, vol. 25, no. 5, pp. 548-558, May 2014. (in Korean)   과학기술학회마을   DOI
4 MIL-STD-188-125-1, "High-altitude electromagnetic pulse(HEMP) protection for ground-based C41 facilities performing critical, time-urgent missions part 1 fixed facilities", Apr. 2005.
5 Lawrence F. Babcock, "Shielding circuits from EMP", IEEE Trans. on EMC, vol. 9, no. 2, pp. 45-48, Sep. 1967.