Browse > Article
http://dx.doi.org/10.4313/JKEM.2021.34.2.136

Condition Monitoring Technique for Heating Cables by Detecting Discharge Signal  

Kim, Dong-Eon (Department of Electrical and Electronics Engineering, Korea Maritime and Ocean University)
Kim, Nam-Hoon (Department of Electrical and Electronics Engineering, Korea Maritime and Ocean University)
Lim, Seung-Hyun (Department of Electrical and Electronics Engineering, Korea Maritime and Ocean University)
Kil, Gyung-Suk (Department of Electrical and Electronics Engineering, Korea Maritime and Ocean University)
Publication Information
Journal of the Korean Institute of Electrical and Electronic Material Engineers / v.34, no.2, 2021 , pp. 136-141 More about this Journal
Abstract
Heating cables, widely used in office buildings, factories, streets and railways, deteriorate in electrical insulation during operation. The insulation deterioration of heating cables leads to electric discharges that can cause electrical fires. With this background, this paper dealt with a condition monitoring technique for heating cables by the analysis of discharge signals to prevent electrical fires. Insulation deterioration was simulated using an arc generator specified in UL1699 under AC operation, and the characteristic and propagation of discharge signals were analyzed on a 100 meter-long heating cable. Discharge signals produced by insulation deterioration were detected as a voltage pulse because they are as small as a few mV and they are attenuated through propagation path. The frequency spectrum of discharge signals mainly existed in the range from 70 kHz to 110 kHz, and the maximum attenuation of the signal was 84.8% at 100 meters away from the discharge point. Based on the experimental results, a monitoring device, which is composed of a high pass filter with the cut-off frequency of 70 kHz, a comparator, a wave shaper and a microprocessor, was designed and fabricated. Also, an algorithm was designed to discriminate the discharge signal in the presence of noise, compared with the pulse repetition period and the number of pulse counts per 100ms. In the experiment, the result showed that the prototype monitoring device could detect and discriminate the discharge signals produced at every discharge point on a heating cable.
Keywords
Heating cable; Insulation deterioration; Electric fire; Pulse repetition; Pulse count; Monitoring device;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 National Fire Data System, http://www.nfds.go.kr (2020).
2 G. S. Kil, K. S. Jung, D. W. Park, S. J. Kim, and J. S. Han, J. Korean Inst. Electr. Electron. Mater. Eng., 23, 554 (2010). [DOI: https://doi.org/10.4313/JKEM.2010.23.7.554]   DOI
3 H. E. Jo, C . H. Jin, D. W. Park, G. S. Kil, and C . H. Ahn, J. Korean Inst. Electr. Electron. Mater. Eng., 25, 147 (2012). [DOI: https://doi.org/10.4313/JKEM.2012.25.2.147]   DOI
4 W. H. Kim, G. Wang, G. S. Kil, and H. K. Ji, J. Korean Inst. Electr. Electron. Mater. Eng., 31, 412 (2018). [DOI: https://doi.org/10.4313/JKEM.2018.31.6.412]   DOI
5 H. K. Ji, Ph.D. Thesis, p. 9-18, Korea Maritime and Ocean University, Busan (2018).
6 G. D. Gregory, K. Wong, and R. F. Dvorak, IEEE Trans. Ind. Appl., 40, 1006 (2004). [DOI: https://doi.org//10.1109/TIA.2004.831287]   DOI
7 Underwriters Laboratories, UL1699-Standard for Arc-Fault Circuit-Interrupters, 2006.
8 Y. H. Md Thayoob, A. M. Ariffin, and S. Sulaiman, Proc. 2010 International Conference on Computer Applications and Industrial Electronics (IEEE, Kuala Lumpur, Malaysia, 2010) p. 665. [DOI: https://doi.org/10.1109/ICCAIE.2010.5735018]   DOI
9 H. W. Ott, Noise Reduction Techniques in Electronic Systems (John Wiley & Sons, Inc., New York, 1988) p. 129.
10 C. Li, F. Dawson, H. Kojori, C. Meyers, and E. Yue, Proc. World Aviation Congress & Exposition (SAE Technical Paper Series, Montreal, 2003) p. 590. [DOI: https://doi.org/10.4271/2003-01-3037]   DOI