Browse > Article
http://dx.doi.org/10.4313/JKEM.2019.32.4.263

A Case Study of Degradation Characteristics for Rod-Insulator on Catenary System in Electric Railway  

Jung, Hosung (Smart Electrical & Signaling Division, Korea Railroad Research Institute)
Park, Young (Department of Electrical System Engineering, Hanbat National University)
Publication Information
Journal of the Korean Institute of Electrical and Electronic Material Engineers / v.32, no.4, 2019 , pp. 263-266 More about this Journal
Abstract
In the Airport Railroad, the Yeongjong Bridge has a length of 4,420 m and connects Yeongjong Island with the mainland of Incheon City. The bridge is a two-level structure, consisting of a six-lane road at the upper level and a combination of a road and railroad at the lower level. The environmental conditions for the electric railway come mainly from the salt injury area and a heavy industry zone, and the maintenance cycles are determined differently depending on these conditions. This study analyzed the deterioration characteristics of long rod insulators produced with a movable ceramic bracket and polymer materials in the Yeongjong Bridge section of the Airport Railway operating in the salt injury area according to the material characteristics. Comparison of the corona measurements when the insulators were cleaned at the same time showed that the polymer insulator had a higher insulation performance than the ceramic insulator.
Keywords
Catenary system; Rod-insulator; Electric railway;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 H. Kim, Trans. Korean. Inst. Elect. Eng., 62, 1177 (2013). [DOI: https://doi.org/10.5370/KIEE.2013.62.8.1177]   DOI
2 Y. S. Cho, G. S. Song, Y. S. Choi, and T. S. Park, Trans. Korean. Inst. Elect. Eng., 60, 588 (2011). [DOI: https://doi.org/10.5370/KIEE.2011.60.3.588]   DOI
3 B. K. Ron, and Y. B. Kim, Spring Conference & Processing (the Korean Society for Railway, Changwon, Korea, 2010) p. 80.
4 B. Y. Yu and C. O. Kim, J. Korean Soc. Saf., 26, 26 (2011). [DOI: https://doi.org/10.14346/JKOSOS.2011.26.2.026]
5 EPRI, Guide to Corona and Arcing Inspection of Overhead Transmission Lines, EPRI Report 1001910, 2002.
6 KRS PW 0014-18, Long Pod Insulator (Polymer type T-m), Korean Railway Standard, 2018.
7 J. T. Oh, S. Hwang, and S. Pyo, J. Korean Soc. Railw., 19, 785 (2016). [DOI: https://doi.org/10.7782/JKSR.2016.19.6.785]   DOI
8 Y. Park, H. S. Jung, C. M. Park, and S. H. Jang, Trans. Korean. Inst. Elect. Eng., 60, 1788 (2011). [DOI: https://doi.org/10.5370/KIEE.2011.60.9.1788]   DOI
9 S. Y. Oh, Y. Park, Y. H. Cho, K. W. Lee, and J. T. Song, J. Korean Inst. Electr. Electron. Mater. Eng., 24, 497 (2011).   DOI
10 Y. Park, K. Lee, C. Park, and S. Y. Kwon, Trans. Korean. Inst. Elect. Eng., 62, 886 (2013). [DOI: https://doi.org/10.5370/KIEE.2013.62.6.886]   DOI
11 K. Lee, Trans. Korean. Inst. Elect. Eng., 62, 1820 (2013). [DOI: https://doi.org/10.5370/KIEE.2013.62.12.1820]   DOI
12 Web-page: New Airport Hiway, https://www.hiway21.com/(2014).