Browse > Article
http://dx.doi.org/10.4313/JKEM.2016.29.7.424

Analysis on Power Burden of HTSC Module due to Fault Current's Amplitude of a Flux-Lock Type SFCL with Two Triggering Currents  

Han, Tae-Hee (Department of Aero Materials Engineering, Jungwon University)
Lim, Sung-Hun (School of Electrical Engineering, Soongsil University)
Publication Information
Journal of the Korean Institute of Electrical and Electronic Material Engineers / v.29, no.7, 2016 , pp. 424-428 More about this Journal
Abstract
In this paper, the power burden of High-TC superconducting (HTSC) module comprising the flux-lock type superconducting fault current limiter (SFCL) with two triggering currents during the fault period was analyzed. The short-circuit tests for the simulated power system with the SFCL in the different fault positions, which were expected to affect the amplitude of the fault current, were carried out. Through the comparative analysis on the power burden of the HTSC modules, the proposed flux-lock type SFCL was confirmed to be effective to divide into two power burdens according to the amplitude of the fault currents.
Keywords
Flux-lock type superconducting fault current limiter (SFCL); Two triggering currents; Fault positions; Power burden;
Citations & Related Records
연도 인용수 순위
  • Reference
1 M. Noe and B. R. Oswald, IEEE Trans. on Appl. Supercond., 9, 2 (1999). [DOI: http://dx.doi.org/10.1109/77.783552]   DOI
2 L. Ye, L. Z. Lin, and K. P. Juengst, IEEE Trans. on Appl. Supercond., 12, 1 (2002). [DOI: http://dx.doi.org/10.1109/TASC.2002.1018344]   DOI
3 L. Ye and A. Campbell, IEEE Trans. on Appl. Supercond., 16, 2 (2006). [DOI: http://dx.doi.org/10.1109/TASC.2006.870526]   DOI
4 H. Shimiau, Y. Yokomizu, and T. Matsumura, IEEE Trans. on Appl. Supercond., 14, 2 (2004). [DOI: http://dx.doi.org/10.1109/TASC.2004.828450]   DOI
5 T. Janowski, S. Kozak, B. K. Kucewicz, G. Wojtasiewicz, and J. Kozak, IEEE Trans. on Appl. Supercond., 17, 2 (2007). [DOI: http://dx.doi.org/10.1109/TASC.2007.898134]   DOI
6 T. Janowski, H. D. Stryczewska, S. Kozak, B. K. Kucewicz, G. Wojtasiewicz, J. Kozak, P. Surdacki, and H. Malinowski, IEEE Trans. on Appl. Supercond., 14, 2 (2004). [DOI: http://dx.doi.org/10.1109/TASC.2004.830298]   DOI
7 S. H. Lim, Physica C, 470, 1631 (2010). [DOI: http://dx.doi.org/10.1016/j.physc.2010.05.177]   DOI
8 S. C. Ko, S. H. Lim, and T. H. Han, Physica C, 484, 263 (2013). [DOI: http://dx.doi.org/10.1016/j.physc.2012.03.041]   DOI
9 J. H. Lee and S. K. Joo, IEEE Trans. on Appl. Supercond., 23, 3 (2013). [DOI: http://dx.doi.org/10.1109/TASC.2013.2266401]   DOI
10 L. Salasoo, A. F. Imece, R. W. Delmerico, and R. D. Wyatt, IEEE Trans. on Appl. Supercond., 5, 2 (1995). [DOI: http://dx.doi.org/10.1109/77.402739]   DOI