Partial discharge(PD) test can be performed either when the rotating machine is not operating(off-line) or during normal machine operation(on-line). This paper presents an on-line and off-line PD test on a large hydro-generator and induction motor using the same PD acquisition system(PDAS) and ceramic coupler(CC) sensor. PD signal characteristics of CC sensor proved similar with that of epoxy mica coupler(EMC) sensor as a results of PD test for simulated defect winding and frequency response test. A comparison of on-line and off-line PD test for PD characteristic parameters-phase resolved PD(PRPD), maximum PD value(Qmax) and PD occurrence energy(POE)-indicated that on-line PD test could reliably and effectively diagnose insulation conditions which were verified by off-line PD test.
Keywords
PD; On-line PD test; Off-line PD test; Rotating machine; Insulation;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 H. Zhu, V, Green, M. Sasic, and S. Halliburton, 'Increased sensitivity couplers for In-service PD measurement in rotating machines', IEEE Transactions on Energy Conversion, Vol. 14, No. 4, p. 1184, 1999   DOI   ScienceOn
2 IEEE Std 1434-2000, 'IEEE Trial-Use Guide to the Measurement of Partial Disch-arges in Rotating Machinery', Aug., 2000
3 W. Hutter, 'Partial discharges-Part XII:Partial discharge detection in rotating electrical machines', IEEE Electrical Insulation Magazine, Vol. 8, No. 3, p. 21, 1992
4 강동식, 선종호, 황돈하, 윤영호, 신병철, 오봉근, '13 kV급 수력발전기 고정자 권선용 on-line 부분방전 측정 시스템 개발 및 현장적용 평가', 전기학회논문지, 55C권, 4호, p. 189, 2006   과학기술학회마을
5 오봉근, 김현일, 강성화, 임기조, '수력발전기 고정자 노후권선의 모의결함 시편에 대한 부분 방전 파라미터 변화분석', 전기전자재료학회논문지, 20권, 7호, p. 645, 2007   과학기술학회마을   DOI
6 C. Hudon and M. Melec, 'Partial discharge signal interpretation for generator diagnostics', IEEE Transactions on Dielectrics and Electrical Insulation, Vol. 12, No. 2, p. 297, 2005   DOI   ScienceOn
7 박재준, 이성룡, 문대철, '고압전동기 고정자권선의 PRPD 부분방전 결함신호 해석', 전기전자재료학회논문지, 19권, 10호, p. 942, 2006   과학기술학회마을   DOI