Study on Efficiency for Underground Heat Transfer of Metal Heat Exchanger  

Song, Jae-Yong (SanHa E&C Co., Ltd)
Kim, Ki-Joon (SanHa E&C Co., Ltd)
An, Sang-Gon (SanHa E&C Co., Ltd)
Kim, Jin-Sung (Rural Research Institute, Korea Rural Community Corporation)
Jeong, Gyo-Cheol (Dept. of Earth and Environmental Sciences, Andong National University)
Publication Information
The Journal of Engineering Geology / v.25, no.1, 2015 , pp. 131-148 More about this Journal
Abstract
The purpose of this study is to analyze and compare the heat transfer efficiency of using copper pipe, stainless pipe and traditional PE pipe commonly used for geothermal heat exchanger, with aims at seeking improved methods. In addition, the varying efficiency of heat transfer from ground heat and groundwater heat was assessed and its applicability was discussed. Design parameters for empirical field study were derived by controlling flow rate, velocity and caliber of pipes of the heat exchanger after the thermal efficiency of the heat exchanger material was evaluated. The heat exchange efficiency and effective thermal conductivity were measured with changing pattern through field thermal efficiency and thermal response test. Experimental results show that the metal material showed higher heat transfer efficiency than the PE pipe. Although the heat transfer efficiency was not high with the increase of the pipe diameter in the flow rate, it was high with the increase of the pipe diameter in the velocity.
Keywords
heat exchanger; heat efficiency; heat conductivity; metal;
Citations & Related Records
Times Cited By KSCI : 5  (Citation Analysis)
연도 인용수 순위
1 Barbier, E., 2002, Geothermal energy technology and current status: an overview, Renewable and Sustainable Energy Reviews, 6(1-2), 3-65.   DOI
2 Cho, H. N., Lee, D. H., and Jeong, G. C., 2012, Effciency of geothermal energy generation assessed from measurements of deep depth geothermal conductivity, The Journal of Enginerring Geology, 22(2), 233-241 (in Korean with English abstract).   DOI   ScienceOn
3 Kim, O. J., Lee, K. H., and Kim, M. S., 2008, A study on improving the efficiency of ground heat exchanger, The Korea Society of Mechanical Engineers Autumn Conference, 11, 2008, 3142-3147 (in Korean with English abstract).
4 Lee, M. T., Kim, Y. I., and Kang, B. H., 2007, Dynamic simulation of ground source heat pump with a vertical U-tube ground heat exchanger, Korean journal of airconditioning and refrigeration engineering, 19(5), 372-378 (in Korean with English abstract).
5 Lee, C. H., Lee, K. J., Choi, H. S., and Choi, H. P., 2009, Thermal conductivity and viscosity of graphite-added bentonite grout for backfilling ground heat exchanger, Transactions of the Korea society of geothermal energy engineers, 5(1), 19-24 (in Korean with English abstract).
6 No, S. T., 2014, An analysis of borehole depth variation of vertical closed loop ground heat exchanger with various design conditions, Journal of the Regional Association of Architectural Institute of the Korea, 16(1), 233-238 (in Korean with English abstract).
7 Lee, J. Y., 2009, Current status of ground source heat pumps in korea, Renewable and Sustainable Energy Reviews, 13(6), 1560-1568 (in Korean with English).   DOI
8 Lund, J. W., Freeston, D. H., and Boyd, T. L., 2011, Direct utilization of geothermal energy 2010 worldwide review, Geothermics, 40(3), 159-180.   DOI   ScienceOn
9 Massachusetts Institute of Technology (MIT), 2006, The future of geothermal energy, Idaho National Laboratory, 200p.
10 Park, Y. B., Park, J. B., Lim, H. S., and Baek, S. K., 2007, Economic analsys of cooling-heating system using ground source heat in multi family apartment, Journal of the Korean Geoenvironmental Society, 8(3), 11-18 (in Korean with English abstract).