Abstract
Cooling towers water has frequently been known as a source of infection in outbreaks of Legionnaires' disease and a source of indoor air pollution. However, there have been a few reports on the presence of Legionella in cooling towers water and aerosols of various public facilities. This study was carried out to investigate the indoor and outdoor dis-tribution of Legionella spp and microbe from 132 cooling towers water of public facilities detected 1. pneumophila in Seoul and Gyeonggi-Do areas. The results showed that the Lpneumophila among the selected 132 cooling towers was detected mostly in July (12.0%), followed by August (4.0%) and June, September no-detected. The 1. pneumophiia in public facilities was detected mostly in department store (27.3%), followed by hospital (8.7%), office building (5.9%), big market (5.0%) and hotel, subway no-detected. The pH values of cooling towers water with presence of 1. pneumophila showed mostly 8.0 or higher (9.5%), followed by 7.0~8.0 (6.8%), lower 7.0 no-detected. The tem-perature of cooling towers water with presence of L pnemophila showed mostly 30℃ or higher (9.8%), followed by 26~30℃ (6.9%), lower 25℃ no-detected. The turbidity of cooling towers water with presence of 1. pneumaphila showed mostly 1-2 M (8.8%), followed by above 2 NTU (5.9%), lower 1 NTU no-detected. The correlation coef-ficient between indoor and outdoor concentration of microbes in public facilities showed 0.67 in Legionella spy. (p>0.05), 0.93 in bacteria (p<0.01), 0.94 in fungus (p<0.01), 0.98 in coilform (p<0.01), respectively.
Keywords
Legionella pneumophila; Indoor/Outdoor concentration; Microbes;
Citations & Related Records
연도 인용수 순위
  • Reference
1 박석기, 황영옥, 정지헌, 정윤태 : 서울시내 다중이용시설 냉각탑수의 레지오넬라균 분포 및 혈청학적특성. 서울시보건환경연구원보, 35, 21-26, 1999
2 Capabianca, R. M., Jurinski, V. B. and Jurinski, J. B. : A comparison of Legionella and other bacteria concentrations in cooling tower water. Appl. Occup. Environ. Hyg., 9(5), 358-361, 1994   DOI   ScienceOn
3 Glick, T. H., Gregg, M. B., Berman, B., Malison, G., Phodes, W. W. and Kassanoff. Pontiac fever : An epi-demic of unknown etiology in a heath department. 1. Clinical and Epidemiologic aspects. Am. J. Epide-miol., 107, 149, 1978   DOI
4 정종학, 강복수, 김석범, 사공준 : 환경수(냉각탑수)로부터 Legionella속 균의 분리. 영남의대학술지, 5(1), 1988
5 Pope, D. H., Soracco, R. J., Gill, H. K. and Fliermans, C. B. : Growth of Legionella pneumophila in two membered culturer with green algae and cyanobacteria. Curr. Microbil, 7, 319-322, 1982   DOI
6 김정순, 이성우, 심한섭, 오대규, 조민기, 오희복, 우세홍, 정윤섭 : 1984년 7월 K병원 중환자실을 중심으로 집단발생한 비폐렴성 Legionellosis(pontiac fever)에 관한 역학적 연구. 한국역학회지, 7, 44, 1985
7 Yocom, J. E. : Indoor-outdoor air quality relation-ships - a critical review. JAPCA, 32, 1982
8 백남원, 김윤신, 김광종 : 지하공간의 공기오염 및 공기 중 미량유해물질에 관한 조사연구. 한국환경과학연구협의회, 1989
9 환경부 : 지하생활공간 공기질관리법. 2001
10 Ikedo. Yabuuchi : Ecological studies of Legionella species. I, viable counts of Legionella pneumophila in cooling tower water, Microbiol. Immunol., 30(5) 413-423, 1986   DOI
11 환경부 : 지하생활공간 공기질 관리법 시행규칙. 관보 13816호, 1998
12 서울특별시 : 지하생활공간 공기오염 저감방안에 관한 연구. 1997
13 Krieg, N. R. and Holt, J. G. : Bergey's manual of sys-tematic bacteriology. William and Wilkins, Balti-more, 498-506, 1984
14 국립보건원 : 개정 감염병 실험실 진단지침. 1996
15 厚生省 生活衛生局 企劃課 : Legionellosis 防止指針. 財團法人 Building 管理敎育 Center, 1993
16 Chanpin, E. S. : Human activity patterns in the city : Things people do in time and in space. John Wiley and Sons., New York, 1974
17 McDade, J. E., Shepard, C. C., Fraser, D. W., Tsai, T. R., Redus, M. A. and Dowdle, W. R. : Legionnaires disease: Isolation of a bacterium and demonstation of its role in other respiratory disease. N. Engl. J. Med., 297, 1197, 1977   DOI   ScienceOn
18 박석기, 황영옥, 정지헌, 정윤태 : 서울시내 다중 이용시설 냉각탑수의 레지오넬라균 분포 및 혈청학적특정 (1994-1998) 서울시보건환경연구원보, 34, 10-16, 1998
19 Meers, P. D., Goh, K. T. and Lim, E. W. : Legionella species, serogroups and subgroups found in the envi-ronment in Singapore. Ann Acad Med Singapore, 18(4), 375-8, 1989
20 Tison, D. L., Pope, D. H., Cherry, W. B. and Fliermans, C. B. : Growth of Legionella pneumophila in association with blue-green algae(Cyanobacteria). Appl. Environ. Microbiol., 39, 456-459, 1980
21 김윤신 : 실내공기오염에 관한 보건학적 고찰. 대한보건협회지, 9(3), 27-39, 1983
22 식품의약청안전청 : 식품공전, 2000
23 Kusnetsov, J. M., Jousimies-Somer, H. R., Nev-alainen, A. L. and Martikainen, P. J. : Isolation of Legionella from water samples using various culture methods. J. Appl. Bacteriol, 76(2), 155-62, 1994   DOI
24 Fliermans, C. B., Cherry, W. B., Orrison, L. H., Smith, S. J., Tison, D. L. and Pop, D. H. : Ecological distribution of Legionella pneumophila. Appl. Environ. Microbiol., 41, 9-16, 1981
25 Fraser, D. W. : Legionnaires' disease: four summer' harvest. Am. J. Med., 68, 1-2, 1980   DOI   PUBMED   ScienceOn
26 환경부 : 먹는물수질공정시험법 (2000.7.1개정). 2000
27 이용우, 성원근, 오현수, 오희복, 박미연, 이명숙, 박경식, 백승복 : Legionella spp.의 감염 및 분포에 관한 연구. 국립보건원보, 23, 297-307, 1986
28 Leoni, P. P. and Legani : Comparison of selective procedures for isolation and enumeration of Legionella species from hot water system. J. Applied Microbioi., 90, 27-33, 2001   DOI   ScienceOn
29 Winn, W. R. Jr. : Legionnaires' disease: Historical perspective. Clin. Microbiol, Rev., 1, 60-81, 1988   DOI
30 Feeley, J. C., Gorman, G. W., Weaver, R. E., Mackel, D. C. and Smith, H. W. : Primary isolation media for legionnaires disease bacterium. J. Clin. Microbiol., 8, 320-325, 1978
31 김권범, 김우주, 김민자, 박승철, 유세화, 섬희선, 함희진, 박석기 : 서울시내 대형건물 냉각탑 수의 레지오넬라균의 오염도 조사와 분자형별 분석에 관한 연구. 감염, 30, 207-217, 1998