Manufacturing and Characteristics Analysis of a Testing Device for the Evaluation of a Distribution Board Management System  

Ko, Wan Su (Department of Fire Safety Engineering, Jeonju University)
Lee, Byung Seol (Soejoeng Electric Company, LTD)
Choi, Chung Seog (Department of Fire Safety Engineering, Jeonju University)
Publication Information
Journal of the Korean Society of Safety / v.34, no.5, 2019 , pp. 31-36 More about this Journal
Abstract
This study made a testing device to evaluate the distribution board management system. Power was supplied to the testing device using a loading-back method and the voltage applied to it was 440 V at the same turn ratio. When the human body electric shock current is 30 mA, the breaking time is set to be less than 240 ms while 30~45 mA current is flowing. The test result shows that in the case of the R-phase it was measured to be 5.19 Hz (193 ms). And the S-phase and T-phase were perfectly cut off at 5.39 Hz (186 ms) and 5.71 Hz (175 ms), respectively. When the human body electric shock current is 60mA, the breaking time is set to be less than 120 ms while 45~75 mA current is flowing. The test result shows that the R-phase, S-phase, and T-phase were accurately cut off at 8.39 Hz (11 ms), 8.87Hz (113 ms) and 9.69 Hz (103 ms), respectively. When the human body electric shock current is 90 mA, the breaking time is set to be less than 48 ms while 75 mA current is flowing. The test result shows that the R-phase, S-phase, and T-phase were accurately cut off at 19.8 Hz (50.4 ms), 16.9 Hz (59.2 ms), and 17.9 Hz (56.0 ms), respectively. That is, the developed testing device satisfied all the requirements of the distribution board evaluation criteria, and it becomes available for the performance evaluation of the distribution board management system.
Keywords
testing device; distribution board management system; electric shock current; breaking time;
Citations & Related Records
Times Cited By KSCI : 5  (Citation Analysis)
연도 인용수 순위
1 S. K. Lee, "Electrical Disaster Statistics in Korea", KESCO, 2016.
2 Korean Standards Association, "KS C IEC 61439-1, "Distributing and Control Board for Low Voltage", 2014.
3 Korea Electrical Manufacturers Cooperative, "SPS-KEMC 2102-610, Low Voltage Distributing Board", 2008.
4 C. S. Choi and S. Y. Hahn, "Study on the Resistivity Leakage Current Detection and Properties Analysis of Electrical Installation", Proceeding of Fall Annual Conference of Korean Institute of Electrical Engineers, pp. 301-304, 2008.
5 J. H. Lee and C. S. Choi, "Damage Pattern and Operation Characteristics of a Thermal Magnetic Type MCCB according to Thermal Stress", J. Korean Soc. Saf., Vol. 28, No. 3, pp. 69-73, 2013.   DOI
6 C. S. Choi, K. M. Shong, D. O. Kim, D. W. Kim and Y. S. Kim, "A Study on the Analysis of Heat and Metallurgical Structure of Connection Parts for Residual Current Protective Devices", Vol. 18, No. 4, Fire Science and Engineering, pp. 57-63, 2004.
7 S. Y. Hanh, "Earth Resistance Leakage Current Meter", Republic of Korea Patent Office, 10-0771583, 2007.
8 B. S. Lee and C. S. Choi, "A Study on the Contact Resistance of Plug-In MCCB Placed in Distributing Board", Proceeding of Spring Annual Conference of Fire Science and Engineering, pp. 56-57, 2013.
9 B. S. Lee, C. S. Choi, "A Study on the Development of a Work Operation Process Chart for Smart Distribution Board Fabrication", J. Korean Soc. Saf., Vol. 32, No. 3, pp. 15-20, 2017.   DOI
10 B. S. Lee and C. S. Choi, "A Study on the Fabrication of the Sensor Module for the Detection of Resistive Leakage Current (Igr) in Real Time and Its Reliability Evaluation", J. Korean Soc. Saf., Vol. 33, No. 1, pp. 28-34, 2018.   DOI
11 W. S. Ko, B. S. Lee and C. S. Choi, "Process Development of a Standard Operating Procedure (SOP) for the Manufacturing of Standardized Distribution Boards", J. Korean Soc. Saf., Vol. 33, No. 5, pp. 21-27, 2018.   DOI