This paper describes the fusing time characteristics of Light PVC Sheathed Circular Cord(VCTF) and Tray Frame Retardant(TFR) cables according to increased temperature under over current condition. The experimental equation will be used to determine the validity and reliability of the test results. The over current flowed 3, 5 and 10 times higher than the amount of allowable current using DC power supply with DAQ(Data Acquisition) measurement system. An infrared radiation heater, which was controlled by a variable AC auto transformer, was used to increase the temperature from room temperature to 50, 100 and 150 degrees Celsius. First, two type of cables were analyzed those with different cross-sectional areas with in the same structure and those with different structures with in the same cross-sectional areas. Then, it was determined how fusing time had been influenced according to the cross-sectional areas and different structures, respectively. The cable resistance was increased by joule heating according to increasing temperature. Therefore, the allowable current of cable is decreased. Finally, the fusing time of the cable was decreased due to increased temperatures at current flow, which were 3 times the amount of allowable current. The instantaneous breakdown was observed when current flow was 5 and 10 times over the amount of allowable current. The fusing time is directly affected by the structure of cable insulation.
Keywords
fusing time; allowable current; breakdown; VCTF; TFR;
Citations & Related Records
연도 인용수 순위
  • Reference
1 S. C. Kim, J. Y. Kim and K. S. Bang, "Experimental Study of Fire Characteristics of a Tray Flame Retardant Cable", J. Korean Soc. Saf., Vol. 28, No. 3, pp. 39-43, 2013.   DOI
2 C. S. Choi, H. K. Kim and D. O. Kim, "A Study on the Characteristics Analysis of Strands Melted by Over Current", J. Korean Soc. Saf., Vol. 19, No. 1, pp. 60-65, 2004.
3 K. M. Shong and Y. S. Roh, "A Study on Discrimination between Short-Circuit and Overload based on the Characteristics of the Fusing Current of an Electrical Wire", Journal of KIEE, Vol. 21, No. 10, pp. 176-180, 2007.
4 K. M. Shong, C. S. Choi, D. W. Kim and H. R. Kwak, "A Study on the Growing Characteristics of Dendrite Structure of Melted Wire Deteriorated by Over Current", KIEE Summer Conference, pp. 1463-1465, 2003.
5 IEC 60364-5-54, "Selection and Erection of Electrical Equipment-Earthing Arrangements and Protective Conductors, 2002.10.29.
6 IEC 60724, "Short-circuit Temperature Limits of Electric Cables with Rated Voltages of 1 kV (Um = 1.2 kV) and 3 kV(Um = 3.6 kV)", 2005.2.28.
7 B. J. Kim and J. H. Kim, "A Preliminary Study on Transient State Characteristics of Cable by Over Current", KIIEE Annual Spring Conference, pp. 238-239, 2014.
8 IEC 60364-4-43, "Protection for safety-Protection Against Overcurrent", 2002.8.31.