Browse > Article
http://dx.doi.org/10.14346/JKOSOS.2017.32.4.16

An Experimental Study on Droplet Size according to Discharge Coefficient of Sprinkler Head  

Hur, Min Noung (Korea Fire Institude)
Shin, Changsub (Department of Safety Engineering, Chungbuk National University)
Publication Information
Journal of the Korean Society of Safety / v.32, no.4, 2017 , pp. 16-21 More about this Journal
Abstract
The sprinkler system is a basic fire extinguishing system that uses water as an extinguishing agent. In order to evaluate the fire extinguishing performance of the sprinkler system, information such as the discharge angle, discharge speed, discharge pressure, flow rate, and water droplet size of the installed head are required. However, there is a lack of research on droplets size compared to other requirements. In this study, to evaluate the extinguishing characteristics of sprinkler system, the droplet size distribution was measured for various types of sprinkler heads actually used. The size of the droplet was measured using laser diffraction method. The 50% cumulative volume distribution ($D_{v50}$) according to discharge coefficient(K factor) was $540{\mu}m{\sim}695{\mu}m$ for K50, $542{\mu}m{\sim}1,192{\mu}m$ for K80, $980{\mu}m{\sim}1,223{\mu}m$ for K115 and $1,188{\mu}m{\sim}1,234{\mu}m$ for K202. Based on the measured results, the vaeiance of the droplet particle distribution and the distribution ($D_{v50}$) according to discharge coefficient(K factor) was $540{\mu}m{\sim}695{\mu}m$ for K50, $542{\mu}m{\sim}1,192{\mu}m$ for K80, $980{\mu}m{\sim}1,223{\mu}m$ for K115 and $1,188{\mu}m{\sim}1,234{\mu}m$ for K202. Based on the measured results, the vaeiance of the droplet particle distribution and the Rosin-Rammler index value are presented. As a result of the fire simulation with FDS, it was confirmed that the performance difference occurs according to the water droplet size distribution even when the same amount of water is used. Therefore, the extinguishing performance of the sprinkler system should be evaluated considering the droplet size distribution according to the sprinkler head type.
Keywords
droplet size; 'K' factor; sprinkler head; discharge coefficient;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 J. R. Hall, Jr., "US Experience with Sprinklers", National Fire Protection Association, 2013.
2 MPSS(Ministry of Public Safety and Security, Republic of Korea), "National Fire Safety Codes of Sprinkler Systems (NFSC 103)", 2016.
3 NFPA 13: Standard for the Installation of Sprinkler Systems
4 MPSS(Ministry of Public Safety and Security, Republic of Korea), "Performance-oriented Design Methods and Standards for Fire-fighting Systems", 2016.
5 C. Yao, "Overview of Sprinkler Technology Research", Proceeding of the 5 th International Symposium on Fire Safety Science, Melbourne, Australia, pp. 93-110, 1997.
6 S. C. Kim and J. Y. Kim, "An Experimental Study on the Droplet Size Distribution of Sprinkler Spray for Residential Building", Journal of ILASS-Korea, Vol. 20, No. 3, pp. 175-180, 2015.   DOI
7 MPSS(Ministry of Public Safety and Security, Republic of Korea), "Standards of Model Approval and Inspection Technology for Sprinker Head", 2016.
8 www.sympatec.com/KR/LaserDiffraction/HELOS.html
9 D. T. Sheppard, "Spray Characteristics of Fire Sprinklers", NIST GCR 02-838, 2002.
10 K. McGrattan, S. Hostikka, R. McDermott, J. Floyd, C. Wenschenk and K. Overholt, "Fire Dynamics Simulator, Technical Reference Guide", Vol. I: Mathematical Model, NIST Gaithersburg, Maryland, 6 th Ed., 2013.
11 www.thunderheadeng.com/pyrosim/fundamentals/#room_fire
12 KS B ISO 6182-1(Fire protection-Automatic sprinkler systems-Part 1), 2007.