Browse > Article
http://dx.doi.org/10.14346/JKOSOS.2014.29.6.046

Development and Its Characterization of Earth Plate for Early Streamer Discharge  

Choi, Sang-Won (Occupational Safety Research Department, Occupational Safety and Health Research Institute, KOSHA)
Her, Yong (Youngjin Enterprise Ltd.)
Publication Information
Journal of the Korean Society of Safety / v.29, no.6, 2014 , pp. 46-48 More about this Journal
Abstract
This paper compared and demonstrated the performance of the earth plate for conventional type and early streamer discharging type developed a new plate in order to improve the performance of the ground plate for use in grounding. The results obtained are shown below; early streamer discharge earth plate was high 5 kV on DC flashover voltage and corona discharge current was higher than about 2 times under the same test conditions compared to the conventional earth plate. From the experiential result, streamer discharge earth plate had a function of rapid inflow/out flow than the general ground plane because of by corona discharge current to be generated in the sharp serrated in formed the ground plane when strike current occurred. In the future, the newly developed early streamer discharge ground plate would be beneficial for grounding work to be widely used to promote the convenience and economy of construction.
Keywords
conventional earth plate; early streamer discharging; grounding work;
Citations & Related Records
연도 인용수 순위
  • Reference
1 http://www.yongjingiup.com/et.al.
2 http://www.dongha.co.kr/et.al.
3 http://www.epartsmall.net/3121/et.al.
4 The Discharge Handbook of Publishing Board Compilation of Japan Institute of Electrical Engineers, Discharge Handbook, 1999.
5 Certification of Utility Model Registration, Registration Number 0363237, 2004.
6 H. -G. Lee and S.- W. Choi, "Development and Its Characterization of Earth Plate for Early Streamer Discharge", Spring Conference of The Korean Society of Safety, pp. 85-88, 2006.