A Study on the Unbalanced Current Distribution of HTS Power Cable  

Kim, Jae-Ho (Department of Fire and Disaster Prevention, Daejeon University)
Park, Chung-Hwa (Department of Fire and Disaster Prevention, Daejeon University)
Publication Information
Journal of the Korean Society of Safety / v.27, no.6, 2012 , pp. 43-47 More about this Journal
Abstract
The unbalance currents flow the High Temperature Superconducting (HTS) power cable caused by asymmetrical fault, harmonic distortion and unbalanced load. That problem causes additional loss and leakage field in the HTS power cable, and deteriorates the electric power quality and stability. In addition, large amounts of unbalanced current can cause negative sequence and ground relays to operate. This paper presents an analysis unbalanced three-phase current distribution in HTS power cable caused by unbalanced load condition and grounding methods using PSCAD/EMTDC. The results obtained through the analysis would provide important data for the design of HTS power cables and valid information for their installation in power system.
Keywords
HTS power cable; current distribution; unbalanced load; conducting layer; shield layer;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 J. H. Bang, H. H. Je, J. H. Kim, K. D. Sim, J. Cho, J. Y. Yoon, M. Park and I. K. Yu, "Critical Current, Critical Temperature and Magnetic Field Based EMTDC Model Component for HTS Power Cable" IEEE Trans. Appl. Supercond., Vol. 17, pp. 1726-1729, 2007.   DOI
2 J. H. Kim, M. Park, J. Cho, K. D. Sim, S. H. Kim and I. K. Yu, "Current Distribution Analysis of Conducting and Shield Layers of HTS Power Cable under Utility Fault Condition" IEEE Trans. Appl. Supercond., Vol. 19, pp. 1718-1721, 2009.   DOI
3 S. Honjo, T. Mimura, Y. Kitoh, Y. Noguchi, T. Masuda, H. Yumura, M. Watanabe, M. Ikeuchi, H. Yaguchi and T. Hara, "Status of Superconducti- ng Cable Demonstration Project in Japan" IEEE Trans. Appl. Supercond., Vol. 21, pp. 967-971, 2011.   DOI
4 M. Park, Y. S. Jo and K .S. Ryu, "Recent Activities of HTS Power Application in Korea" Int. J. Appl. Ceram. Technol., Vol. 4, No. 3, pp. 217-224, 2007.   DOI   ScienceOn
5 P. Tixador, N. T. Nguyen, J. M. Rey, T. Lecrevisse, V. Reinbold, C. Chaud, X. Debray, F. Semperger, S. Devaux and C. Pes, "SMES Optimization for High Energy Densities" IEEE Trans. Appl. Supercond., Vol. 22, pp. 5700704, 2012.   DOI
6 J. F. Maguire, J. Yuan, W. Romanosky, F. Schmidt, R. Soika, S. Bratt, F. Durand, C. King, J. McNamara and T. E. Welsh, "Progress and Status of a 2G HTS Power Cable to be Installed in the Long Island Power Authority(LIPA) Grid" IEEE Trans. Appl. Supercond., Vol. 21, pp. 961-966, 2011.   DOI
7 이승렬, 윤재영, 양병모, "국내 실계통에서의 22.9 kV 초전도케이블/한류기 시범적용을 위한 보호 시스템 설계" 한국초전도저온공학회논문지, Vol. 12, No. 3, pp. 25-28, 2010.
8 양병모, 박진우, 이승렬, "22.9kV 고온 초전도 케이블.한류기 스마트 그리드 적용을 위한 초전도 시범사업" 한국초전도저온공학회논문지, Vol. 12, No. 3, pp. 34-38, 2010.
9 S. H. Sohn, H. S. Yang, J. H. Lim, S. R. Oh, S. W. Yim, S. K. Lee, H. M. Jang and S. D. Hwang, "Installation and Power Grid Demonstration of a 22.9kV, 50MVA, High Temperature Superconducting Cable for KEPCO" IEEE Trans. Appl. Supercond., Vol. 22, pp. 5800846, 2012.
10 J. H. Kim, M. Park, M. H. Ali, J. Cho, J. Yoon, S. R. Lee and I. K. Yu, "RTDS Analysis of the Fault Current Characteristics of HTS Power Cable in Utility Power Network" IEEE Trans. Appl. Supercond., Vol. 18, pp. 684-688, 2008.   DOI
11 한국전력공사 전력연구원, "배전용변압기 최적 부하관리 방안 연구" 최종보고서, 2003.
12 장현만, "S전선 초전도 케이블 시스템 개발" 대한전기학회 하계학술대회 논문집, Vol. 2007, No. 11, pp. 23, 2007.